15.2 CONNETION WITHOUT AUXILIARY COIL

The connection diagram below can only be used when there is not an auxiliary coil present and where the power for the
regulator power circuit is obtained from the alternatorphases. The voltage between pins 3 and N should be in the range of
170 to 250 Vac. See below a connection example in a 380Vac phase to phase and 220Vac phase to neutral generator.
For regulator connections in an alternator with a different voltage than what is mentioned in the example, please contact
the regulator manufacturer.
GERADOR
GENERADOR
GENERATOR
CAMPO DA EXCITATRIZ
CAMPO DE LA EXCITATRIZ
EXCITER FIELD
EXCITER FIELD
CHAVE LIG./DESL.
ON/OFF
LLAVE LIG./DESL.
SWITCH
ON/OFF SWITCH
¹ Item not supplied by WEG;
² If there is no Potentiometer connected, keep terminals
³ 10A/250Vac switch to turn ON/OFF the regulator;
JR, JS e JT Jumpers – Sensing voltage selection (pins 1-2 = 160 to 300Vac, pins 2-3 = 320 to 600Vac).
4
5
(opened - paralell, closed - single).
ATTENTION
1. Before connecting the regulator to the generator, verify in the installation manual, the reference
nominal voltage.
2. The sensing voltage can be different than the alternatorphase voltage. Note the point where the
sensing voltage is taken from (middle of the phase or complete phase).
3. If the reference voltage is not equal to the output voltage of the generator, do not make the
connections without consulting the service department.
P1
S1
3
N
R
S
T
F+
AVR-A-OPT-03/C
WRGA-01/C
F-
Sensing Voltage 320 to 600Vac
P2
S2
CHAVE SINGELO / PARALELO
SINGLE/PARALLEL
1- 5
LLAVE SINGELO / PARALELO
SWITCH
SINGLE / PARALLEL SWITCH
1
2
S2
S1
short-circuited;
Analog Voltage Regulator AVR-A-OPT-03
www.weg.net
CONFIGURATION
FOR 320 TO
600V USE JUMP
ON PINS 2 AND 3
POTENCIOMETRO DE AJUSTE
EXTERNO DE TENSÃO (5k
/3W)
POTENCIOMETRO DE AJUSTE
EXTERNAL ADJUSTMENT
EXTERNO DE TENSION (5k
/3W)
POTENTIOMETER (5k/3W) ¹ ²
EXTERNAL ADJUSTMENT
POTENTIOMETER (5k
/3W)
|
4
.
21