7.
When an error occurs or the protection mode is set automatically, the circuit board and
the wired controller will both display the error message.
Error
Meaning
Water Flow
P01
failure
High pressure
P02
protection
Low pressure
P03
protection
T3 Coil
P04
overheat
protection
Exhausting gas
P05
temperature
protection
Analysis
1. Check if water in valve is
2. No water flow
closed or no water in
2. Flow switch failure
2.Check if flow switch is
3. Water system block
blocked or damaged
ïX Z l ](^z_^Z ‰ (]oš Œ
blocked
1. Check if water flow is not
enough or water pump flow is
not enough;
1.Water flow is too small
2. Check if high-pressure
2. High-pressure switch
switch is off9
is damaged9
3.Check if refrigerant system is
3.Refrigerant system
blocked
block9
4. When heat pump is off and
4. EEV dead lock.
turn the heat pump on and off
to check if EEV can be listened
by sound of reset.
1. Lack of gas
1.Check if gas system is leaking
2.Refrigerant system
2. Check if filter is blocked
block9
3. Check ambient Temp. and
3.Exceed heat pump
water temp. is over limitation
operation range
1. Heat Pump fan
blowing area is
1. Check if the blowing area is
blocked
open
2. Evaporator is
2. check if the evaporator is
blocked
blocked
3. T3 coil sensor
3.check if the coil sensor
position was
resistance value is correct
changed
1.Ceheck if refrigerant system
1. Lack of gas
is leaking
2. sensor position was
2.check if the sensor
changed
resistance value is correct
49
Diagnosis
1. Open the valve
2. Change a new flow switch
3.Clean or change a new filter
1. Reinject water or change to a
new pump of larger water flow;
2. Change a new high-pressure
switch
3. change a new filter
4.Change a new EEV
1.Amend the leakage and
reinject the gas
2.change a new filter
1. Put away the blow area
2. Clean the evaporator
3. Change a new sensor
1.Amend the leakage and
reinject the gas
2.Change a new sensor
Solution