Advanced features of the digital controller
This chapter gives an overview of the direct parameters and user
parameters provided by the controller. In the following chapter, you
will learn how you can set up and configure the unit using these
parameters.
Overview of the direct and user parameters
The list of direct parameters is accessible by pressing the B key
for approximately 5 seconds. Refer also to "How to consult and
modify the direct parameters" on page 8.
Parameter
Parameter
group
code
-/-
/23
Measurement unit
-a-
No user or direct parameters accessible
b01
Evaporator inlet water temperature
b02
Evaporator outlet water temperature
When cooling mode is active: inlet
-b-
water temperature of the condenser.
b03
When heating mode is active: inlet
water temperature of the evaporator.
Time delay between pump startup and
c07
compressor startup
Time threshold between the unit
c08
shutdown and the pump shutdown
c10
Total running hours of compressor 1
-c-
c11
Total running hours of compressor 2
Maintenance threshold for
c14
maintenance warning (c10 and c11)
c15
Total running hours of pump
-d-
No user or direct parameters accessible
-f-
No user or direct parameters accessible
To activate remote cool/heat control
0=not active
h06
1=active
(only in case p09=9)
To activate remote on/off control
0=not active
h07
1=active
(only in case p34=23)
-h-
To lock the controller keyboard
h09
0=lock
1=unlock
h10
Serial address for BMS connection
To select address card connection
h23
0=remote user interface connection
1=MODBUS connection
Changeable digital input selection
S7S
0=no function
p09
9=remote cool/heat (only active in
combination with h06)
13=remote dual setpoint
DO NOT SELECT OTHER VALUES
-p-
Changeable digital input selection
S9S
0=no function
p34
13=remote dual setpoint
23=remote on/off (only active in
combination with h07)
DO NOT SELECT OTHER VALUES
Cooling setpoint
r01
r02
Cooling difference
r03
Heating setpoint
-r-
r04
Heating difference
r21
Cooling setpoint 2
r22
Heating setpoint 2
-t-
No user or direct parameters accessible
f-r
h99
Software release version
(*) D=digital, A=analog, I=integer.
(†) –2.0 and –7.0 only applicable for units with glycol applications.
(‡) Used in case dual setpoint is enabled in p09 or p34 and dual setpoint digital input is closed.
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Default
Description
value
0
=°C
1
=°F
0
15
0
0
0
0
1
1
0
9
23
12.0
3.0
30.0
3.0
(‡)
12.0
(‡)
30.0
Read/
Min
Max
Units
Write
0
1
R/W
0.1°C
R
0.1°C
R
0.1°C
R
0
999
1 sec
R/W
0
150
1 min
R/W
x100 hours
R
x100 hours
R
0
100
x100 hours
R/W
x100 hours
R
0
1
R/W
0
1
R/W
0
1
R/W
1
200
R/W
0
1
R/W
0
27
R/W
0
27
R/W
(†)
25.0
0.1°C
R/W
8.0
0.3
19.9
0.1°C
R/W
15.0
50.0
0.1°C
R/W
0.3
19.9
0.1°C
R/W
(†)
25.0
0.1°C
R/W
8.0
15.0
50.0
0.1°C
R/W
R
Parameter
User/
Modbus
(*)
Direct
Address
type
U
5
D
D
102
A
D
103
A
D
104
A
U
238
I
U
239
I
D
122
A
D
123
A
U
241
I
D
126
A
U
14
D
U
15
D
U
16
D
U
256
I
U
11
D
U
277
I
U
329
I
D
41
A
D
42
A
D
43
A
D
44
A
D
55
A
D
56
A
D
208
I
Operation manual
10