Do not place the UPS in a dusty or corrosive environment or near any flammable objects.
This UPS is not designed for outdoor use.
• Keep the ventilation slits clean to dissipate the heat of the UPS.
To prevent overheating of the UPS keep all ventilation openings free from obstruction, and do not place
anything on top of the UPS. Keep the UPS rear panel 20 cm away from the wall or other obstructions
• Use grounded power cable to connect the UPS to the mains supply.
This UPS is equipped with an EMI filter. To prevent potential leakage current hazards ensure that
the AC mains supply is securely grounded.
• Install the UPS close to the mains socket that supply it.The socket must be easily accessible.
• Do not plug laser printers into the UPS because of their high start-up current.
• Do not plug house electric equipments, such as hair dryer, air conditioner, and refrigerator into
the UPS outlets.
- Always switch off the UPS and disconnect the batteries when relocating the UPS. Be aware that,
even when disconnected, charged batteries present a possible electric shock hazard.
- The UPS should be recharged every 2-3 months if unused. When installed and being used the
batteries will be automatically recharged
Storage
If the UPS is unused for an extended period of time it must be stored in a moderate climate.
The batteries should be charged for 12 hours every three months by connecting the UPS to the
utility supply and switching on the input breaker located on the UPS rear panel. Repeat this
procedure every two months if the storage ambient temperature is above 25°C.
0%~90%
200mm/
8 inch
200mm/
8 inch
KEOR LP 1, 2, 3 kVA