Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 91

9 Technical features

MODEL
ITEM
VA
Capacity
Power Factor
Voltage Rating
Frequency Rating
Phase
Input
Power Factor
Generator Input
Input Connection
Voltage
Voltage Regulation
Frequency
(Synchronized
Range)
Frequency
(Battery Mode)
Current
Output
Crest Ratio
Harmonic
Distortion
Output Waveform
Version A
Outlets
Version B
3 101 54
3 101 55
1000 VA
when input voltage is 210~240Vac PF=0.9 (900/1800/2700W)
when input voltage is 185~260Vac PF=0.8 (800/1600/2400W)
when input voltage is 160~300Vac PF=0.7 (700/1400/2100W)
110/140/160-300 VAC (Based on load percentage
0-25% / 25-50% / 50-100%)
Single phase with ground
0.98 (with full linear load)
10 A, IEC 320-C14
within ±1% until low-battery warning
3 Hz or 1 Hz (selectable)
50/60 Hz ±0.1% unless synchronized to line
< 3% at full linear load
< 7% at full non-linear load
3 x IEC 320-C13
(310154)
3 x IEC 320-C13 + 1 FR
(310155)
KEOR LP 1, 2, 3 kVA
3 101 56
3 101 57
2000 VA
45-65 Hz
Supported
230 V
3:1
Pure sine wave
6 x IEC 320-C13
(310156)
3x IEC 320-C13 + 2FR
(310157)
3 101 58
3 101 59
3000 VA
16A, IEC 320-C20
6 x IEC 320-C13
(310158)
6 x IEC 320-C13 + 2 FR
(310159)
43

Publicidad

Tabla de contenido
loading

Tabla de contenido