Any intervention in the refrigeration circuit must be made following the applicable safety regulations: recovery of
refrigeration fluids, nitrogen welds, etc.
Any welding intervention must be made by qualified welders.
For units loaded with R-407-C, refer to specific instructions in the user manual.
Piping can only be replaced by copper pipes according to standard NF EN 12735-I.
Search for leaks:
Never use oxygen or dry air, danger of fire or explosion.
Use dry nitrogen or the mixture of nitrogen and coolant indicated in the plate.
Any substitution of parts different to the ones considered by the manufacturer, any modifications in the
refrigeration circuit, any substitution of refrigeration fluid by a fluid different to the one indicated in the plate or
any use of the unit beyond the limits specified in the unit documentation would result in the cancellation of the
guarantee.
All information must be registered in the unit manual that must be included in the installation project