• The baud rate is binary coded and is coded with the DIP switch block "baud"
(Fig. 6, item 2) according to Tab. 10.
DIP switch no.
Baud rate
1200
2400
4800
9600
19,2 k
38,4 k
57,6 k
76,8 k
115,2 k
0: DIP switch "off"
Tab. 10
• The address of the DigiCon is binary coded and is coded with the DIP switch
block "address" (Fig. 2, item 19) according to Tab. 11.
• The address of the corresponding pumps is determined by adding the signifi-
cances marked "1" and by adding the value of the hard-wired connection to the
corresponding terminals. Examples:
Address of pump 1 at DigiCon no.1(DIP switch 000000): (0)+0=0
Address of pump 4 at DigiCon no.1(DIP switch 000000): (0)+3=3
Address of pump 3 at DigiCon no.12(DIP switch001011): (32+8+4)+2=46
Installation and operating instructions Wilo-Control DigiCon/DigiCon-A