LU-VE URT Instrucciones página 17

Variadores electrónicos de la tensión trifasica. cuadro elèctrico
Tabla de contenido

Publicidad

3Ph 3.0: indicates the type of firmware (for cut phase regulators) and the "release" index (in this case 3.0).
VISUALISATION
AND MESSAGES
V : display only
L :
SW1 switch 1 in the "OFF" position
K :
SW1 switch 1 in the "ON" position
F
: factory configuratiuon
ON
1
2
3
4
Keypad & Display
The following messages appear in rapid sequence on the display when switched on:
rtE-01: indicates the set-up currently active , in this case master regulator with 2 NTC inlets.
the "in" parameter of the following table is then subsequently shown.
Code
ti
SP
Co
in
i 1
i 2
S1
S2
Lh
Jh1
JL1
Jh2
JL2
Jh3
JL3
USP
UPb
Sh
ih
So
io
hi
Lo
dE
Pb
U.S.P.
U.P.b.
S.h.
i.h.
S.o.
i.o.
h.i.
L.o.
d.E.
P.b.
c0
c1
c2
c3
c4
c5
c6
c7
......
LuVe
3Ph 3.0
rtE-01
Meaning
Internal temperature instrument in °C
Set-Point in use (S1 or S2)
Partialisation of voltage supply at output, also visibile on the Service DIGIT
Value of the higher signal at the inlet IN1 or IN2
Value of the signal to the inlet IN 1
Value of the signal to the inlet IN 2
Set point N.1 (SP1)
Set-point N.2 ( SP2)
Max RPM night limit for SP1 and SP2
Output voltage upper limit for jump N.1
Output voltage lower limit for jump N.1
Output voltage upper limit for jump N.2
Output voltage lower limit for jump N.2
Output voltage upper limit for jump N.3
Output voltage lower limit for jump N.3
Set Point output 0-10V for external humidification unit
Proportion. Band output 0-10V for external humidification unit
Input value for output at maximum
Hysteresis on Sh value
Input values for output at zero
IHysteresis on So value
Maximum RPM limit
Minimum RPM limit
Acceleration/Deceleration time
Proportional Band
Set Point output 0-10V for external humidification unit
Proportion. Band output 0-10V for external humidification unit
Input value for output at max
Hysteresis on the value of Sh
Input value for output at zero
Hysteresis on the value of So
Maximum RPM limit
Minimum RPM limit
Acceleration/Deceleration time
Proportional Band
Working modes : rS , rtE , rPr
Input selection mode
Input type : mA , V , NTC
Display conversion from mA to bar , or from V to bar
Set Point position on working diagram
Setting cos-fi motor/s (from 0 a 15)
RL1 service relay drive
Signal selection mode at the analog output "OUT"
- for control of Slave Unit 0-10Vdc
- for control of Spray Unit
Name of configuration in use (if the K DEFAULT parameters are modified,
a separating point appears after every character).
17
ENGLISH
V
L
S1
K
S2
F

Publicidad