LU-VE URT Instrucciones página 19

Variadores electrónicos de la tensión trifasica. cuadro elèctrico
Tabla de contenido

Publicidad

Display
Code
Value
UM
min
MAX
-10,0
+90,0
°C
4,0
20,0
mA
0
15,0
bar
0
25,0
bar
S1
0
30,0
bar
0
45,0
bar
0
5,0
Vdc
0
30,0
bar
0
10,0
Vdc
-10,0
+90,0
°C
4,0
20,0
mA
0
15,0
bar
0
25,0
bar
S2
0
30,0
bar
0
45,0
bar
0
5,0
Vdc
0
30,0
bar
0
10,0
Vdc
Lh
0%
100%
off
Jh
0%
100%
off
JL
0%
100%
off
setting PROCEDURE for S1 – S2 – Lh
1 - Press the"ENTER"+"ESCAPE" keys at the same time: "ProGrA" appears on the display, followed by S1 (for rtE – rPr) Lh (for rS)
2 - Select the parameter to be modified using the "+" key
3 - Then press the "ENTER" key : the display begins to flash .
4 - Use the (+) and (–) keys to reach the required value (the process is speeded up by pressing "ENTER" at the same time)
5 - Press the "ENTER" key : the display stops flashing
To modify another parameter, begin again at point 2 above
6 - • To confirm the selection, press the "ENTER" + "ESCAPE" keys at the same time: "Update" appears on the display and
the preselected configuration is saved and immediately put into operation.
• To exit without changing the current configuration, press"ESCAPE": the word "ESCAPE" appears on the display.
The regulator begins to operate again under the new parameters and the display goes back to showing the value "in"of the
active input.
setting PROCEDURE for Jh & JL (1-2-3)
To eliminate any high-level sound peaks, procede as follows:
1 - Press the"ENTER"+"ESCAPE" keys at the same time: "ProGrA" appears on the display, followed by S1 (for rtE – rPr) Lh (for rS)
2 - Select the Jh1 code with the "+" key
3 - Press ENTER: the display begins to flash and the regulator interrupts the settings and supplies the fan(s) to the value of the set
voltage (default Jh1 = 100).
4 - Press the "+/-" keys to scroll through the regulation field and identify the high-level sound peak, selecting a position slightly above it.
5 - Press ENTER to confirm : the display stops flashing.
6 - Select the JL1 code using the "+" key.
7 - Press ENTER : the display begins to flash.
8 - Pressing "-", select the value of the setting for Jh1: move down and identify the peak of the sound level. Select a position slightly under it.
9 - Press ENTER to confirm : the display stops flashing.
For any other zones of high-level sound, procede in the same manner using Jh/JL 2 e Jh/JL3
10 - • To confirm the choice, press the "ENTER" and "ESCAPE" keys at the same time: "Update" appears on the display.
• To exit without changing the current configuration, pres the "ESCAPE" key: "ESCAPE" appears on the display.
The regulator goes back to ACTIVE operation and the display shows the value of the input signal (in).
MODIFYING THE REGULATION PARAMETERS
Default
Configuration
45,0
rtE-01
14,0
rPr420
10,6
rPr015
17,0
rPr025
17,0
rPr030
25,0
rPr045
2,9
rUu-05
18,5
rPu030
6,0
rUu010
45,0
rtE-01
14,0
rPr420
10,6
rPr015
17,0
rPr025
17,0
rPr030
25,0
rPr045
2,9
rUu-05
18,0
rPu030
6,0
rUu010
100%
All configurations
100%
All configurations
100%
All configurations
Sensor
STE –20/+90°C
4-20 mA
SPR 0-15 bar
SPR 0-25 bar
SPR 0-30 bar
SPR 0-45 bar
0-5 Vdc
0-5 Vdc
0-10 Vdc
STE –20/+90°C
4-20 mA
SPR 0-15 bar
SPR 0-25 bar
SPR 0-30 bar
SPR 0-45 bar
0-5 Vdc
0-5 Vdc
0-10 Vdc
All sensors
Max RPM% Night Limit
All sensors
Upper RPM% Limit for jump 1 – jump 2 – jump 3
All sensors
Lower RPM% Limit for jump 1 – jump 2 – jump 3
19
ENGLISH
Description
Set point 1 (SP1)
Set point 2 (SP2)

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Qe-nqeQe

Tabla de contenido