6.1
Technical Specifications
Output power
Electrical supply network
w Rated input voltage
w Input voltage range
w Frequency
w Power factor
w Leakage current
Load output
w Voltage
w Frequency
w Harmonic distortion
w Overload capacity
w Current
Battery
Environment
w Operating temperature
range
w Relative humidity
w Storage temperature
range
w Altitude
w Noise level
(1)
Depending on the output voltage selected: 100V / 104V / 110V / 120V / 127V, the output power is 1890VA /
1890VA / 2100VA / 2100VA / 2100VA.
(2)
Depending on the output voltage selected: 100V / 104V / 110V / 120V / 127V, the output power is 2500VA /
2500VA / 2500VA / 3000VA / 3000VA.
(3)
Standard output power is 2550 W, 2400 W with an EXB module.
(4)
Values for 33% / 66% / 100% of UPS output.
(5)
Programmable: 100V / 104V / 110V / 120V / 127V using the UPS Config software.
(6)
Frequency-converter mode is programmable using the UPS Config software.
(7)
Depending on the output voltage selected: 100V / 104V / 110V / 120V / 127V, the maximum output current is
18.9A / 18.2A / 19.1A / 17.5A / 16.5A.
(8)
Depending on the output voltage selected: 100V / 104V / 110V / 120V / 127V, the output current is 25A / 24A /
22.7A / 25A / 23.6A.
(9)
EXB is in 3U model only. Standard UPS can be connected with up to 4 EXB.
EX 2200
2100 VA
/
3000 VA
(1)
1650 W
2550 W
Single phase 120 V
55 / 72 / 100 to 142 V
50/60 Hz (autoselection)
Single phase 120 V ±3%
50/60 Hz ±0,5%
< 4% for linear load, < 6% for nonlinear load
102% continuous, 105% 20s, > 130% 1.5s
17.5 A
(7)
6 x 12V - 7 Ah,
6 x 12V - 9 Ah,
sealed lead acid,
sealed lead acid,
maintenance free
maintenance free
EX 3000
EX 3000 XL
/
3000 VA
(2)
2150 W
(3)
(4)
> 0.95
< 2 mA
(5)
(6)
25 A
(8)
without internal
battery
0°C to 40°C (32°F to 104°F )
20% to 90% (without condensation)
-20°C to 40°C (-4°F to 104°F)
1000 m
< 47 dBA
6. Appendices
EXB
(9)
/
(2)
Two 6 x 12 V - 9 Ah
strings, sealed lead acid,
maintenance free
86-86710-00EN A02 - Page 27