6.1 Technical specifications
Output power
AC input power
Voltage
Frequency
Power factor
Load output
Voltage
Frequency
Harmonic distortion (THDV)
Overload capacity
Current
Battery
Environment
Noise level
Operating temperature range
Relative humidity
Leakage current
Storage temperature range
Altitude
Standards and certification
Safety
Performance
EMC
Markings
(1) EXB Module for EX 1000 and EX 1500.
(2) EXB Module for EX 1000 RT and EX 1500 RT.
(3) Output power is 900 W in standard configuration, and 800 W as soon as 1 EXB module is connected.
(4) Output power is 1350 W in standard configuration, and 1250 W as soon as 1 EXB module is connected.
(5) Values for 20% / 33% / 66% / 100% of UPS output.
(6) Adjustable from 200 V to 250 V using the UPS Config software.
(7) Frequency-converter mode is programmable using the UPS Config software.
(8) Nominal values given for 230 V output voltage.
34008097EN/AE - Page 26
EX 700
EX 1000
EX 1000 RT
700 VA / 630 W
1000 VA / 900 W
Single phase 100 / 120 / 140 V / 160 V / 184 V to 284 V
50/60 Hz (autoselection)
> 0.95
Single phase 230 V ±3%
50/60 Hz ±0.5%
< 4% for linear load, < 6% for nonlinear load
102% continuous, 130% 12 s, > 130% 2 s
(8)
3 A
4.3 A
2x12 V - 7 Ah,
3x12 V - 7 Ah,
sealed lead acid,
sealed lead acid,
maintenance free
maintenance free
20% to 90% (without condensation)
IEC/EN 62040-1-1, EN 60950-1 (RD)
IEC/EN 62040-3
EN 50091-2/IEC 62040-2 class B, IEC 61000-4-2/-3/-4/-6-8/-11,
IEC 61000-3-2/-3
CE, TÜV/GS, UL, cUL, CB report
EX 1500
EX 1500 RT
(3)
(4)
1500 VA / 1350 W
(5)
(6)
(7)
(8)
(8)
6.5 A
3x12 V - 9 Ah,
sealed lead acid,
maintenance free
< 38 dBA
0°C to 40°C
< 1,1 mA
-25°C to 40°C
1000 m
(1)
EX EXB
(2)
EX EXB RT
Two 3x12 V - 9 Ah
strings, sealed
lead acid,
maintenance free