Lenze E94ASHE Serie Instrucciones Para El Montaje página 70

Ocultar thumbs Ver también para E94ASHE Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

8
Wiring the device modules
Communication modules
DIP switch
Pos.
Description
Addressing of the bus node
For addressing purposes, every station must be given an unambiguous address.
Valid address range: 1 ... 126
The address can be set freely via the front-panel switch.
Note!
ƒ
ƒ
Switch off the voltage supply of the communication module and then on again
in order to activate changed settings.
Address settings through the DIP switch (device front)
The sum of the values (identical with package labelling) results in the station address to be
set:
Example:
Switch
Package labelling
Switch state
Address (= 23)
Displays
Pos.
Colour
MS
Green
ME
Red
BS
Green
BE
Red
DE
Red
70
For S1 - S7 = OFF (Lenze setting):
When switching on, the configuration set under code C00899 becomes
active.
For one of the switches S1 - S7 = ON:
When switching on, the address resulting from the switch setting becomes
active.
S7
«64»
0
0
Condition
Blinking
On
On
Blinking
On
On
S6
S5
S4
«32»
«16»
«8»
0
1
0
0
16
0
Description
Communication module is supplied with voltage, but has no
connection to the standard device (standard device is switched off,
initialising or does not exist).
Communication module is supplied with voltage and has
established a connection to the standard device.
An error occurred concerning the communication module.
Communication via the communication module is established. The
PROFIBUS is active.
Bus monitoring has responded.
The communication module is not accepted by the standard device
(see notes given in the documentation for the standard device)
S3
S2
S1
«4»
«2»
«1»
1
1
1
4
2
1
EDK94ASH24 DE/EN/FR/ES/IT 3.1

Publicidad

Tabla de contenido
loading

Tabla de contenido