Notes On Circuits And Devices; It Networks - WEG CFW-11 Guia De Instalacion

Ocultar thumbs Ver también para CFW-11:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 25
Installation Guide
1
3
5
(a) Frame sizes F and G
1
Remove cover
(b) Frame size H
Figure 18: Connection of dynamic braking module in standard models of
sizes F, G and H
12 | CFW-11
2
4
6
2
3

NOTES ON CIRCUITS AND DEVICES

ƒ
The power supply that feeds the inverter must have a grounded
neutral. For IT networks some internal components must be
disconnected as shown in
figure 19
ƒ
Provide a disconnect device for the input power supply of the
inverter. This device must disconnect the input power supply for
the inverter when needed (for instance, during servicing).
ƒ
Suitable for circuits with capacity to deliver no more than:
- 100 kA symmetric at 240 V or 480 V when the inverter is protected
by fuses.
- 65 kA symmetric at 240 V or 480 V when the inverter is protected
by reverse-type circuit breakers.
ƒ
The fuse to be used in the input must have current and I
to or smaller than the specification in
[consider the cold current extinction value (not the melting value)]
to protect the input rectifier diodes of the inverter and of the wiring.
ƒ
For compliance with the UL standard and current specifications for
the fuses and circuit breaker, refer to the User's Manual available
for download on: www.weg.net.
ƒ
Motor shielded cable recommended according to IEC 60034-25.
ƒ
Keep motor cables at least 25 cm (9.84 in) distant from other cables
as signal cables, sensor cables, control cables, etc.

IT NETWORKS

When the neutral is not grounded, or the grounding is provided
by a high ohm value resistor or in grounded delta networks ("delta
corner earth").
XE2
XE1
(a) Frame size A
XE1
XE2
(c) Frame size C
Figure 19 (a) to (d): Frame size A to D - Location of Grounding Screws
- Remove for IT networks or delta-grounded
to 22.
t equal
2
tables
A.1,
A.2, A.3
and
A.4
XE2
XE1
(b) Frame size B
XE1
XE2
(d) Frame size D