Micropulse AT Transducer in round profile housing
6
Programming (cont.)
6.2

Programming Output 1

Activate programming mode:
Programming input
La or Lb = "on" until LED comes on
(4 s < t < 8 s)
BTL is in programming mode:
"Error-Message" on both outputs
(10.5 V).
Select Output 1:
1) Programming input La = "on" until
LED stays on (4 s < t < 8 s)
Output 1 selected, both outputs
provide the current position value.
a) Set zero
1) Position magnet 1 at desired zero
point.
2) Programming input La = "on" until
LED stays on (4 s < t < 8 s)
Zero point for Output 1 programmed:
➔ see also: Programming mode
b) Set span
1) Position magnet 1 at desired end
point.
2) Programming input Lb = "on" until
LED stays on (4 s < t < 8 s)
Span for Output 1 programmed:
➔ see also: Programming mode
If the value of the zero point
is further from the zero
point marking than the end
point, the output slope is
automatically set to falling.
Zero = 100 % and
Span = 0 % of output value.
8
english
BTL6-A/G301... with at least 1 magnet in the stroke range
4 s < t <8 s
Programming mode
4 s < t <8 s
4 s < t <8 s
Lb
4 s < t <8 s
Fig. 6-2: Programming Output 1
La = on ➔ Programming input La to 0 V
Lb = on ➔ Programming input Lb to 0 V
Flash time Code
Operating mode
On : Off
/ Lb
La
La
La
Programming mode
LED off
LED on
0.05 s : 0.05 s
LED flashing
rapidly
LED on
0.5 s : 0.5 s
LED flashing
very slowly
LED on
0.05 s : 0.05 s
LED flashing
rapidly
LED on
0.05 s : 0.05 s
LED flashing
rapidly
(output)
(output)