Programming Inputs; Calibration Procedure Notes - Balluff BTL7 Serie Manual De Instrucciones

Ocultar thumbs Ver también para BTL7 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 109
BTL7-A/C/E/G5 _ _ -M _ _ _ _ -K(8)-NEX-SR32/K_ _ _
Micropulse Transducer - Rod Style
6
Calibration procedure
Output
Linear
gradient
transducer
Rising
Falling
Tab. 6-1:
Value table for teach-in and inverting
6.1

Programming inputs

Programming inputs La and Lb must be used in order to
make settings. A programming input at 10 to 30 V
corresponds to activation (high active).
The Balluff BTL7-A-CB02-... calibration box can be used
for this (see Accessories on page 24).
Automatic deactivation!
If no signals are transmitted via the
programming inputs for approx. 10 min,
programming mode is automatically ended.
6.2

Calibration procedure notes

Prerequisites
-
Programming inputs are connected.
-
The transducer is connected to the system controller.
-
Voltage or current values from the transducer can be
read (using a multimeter, the system control or the
calibration box).
Fig. 6-1:
Connecting the BTL7-A-CB02-S... calibration box
14
english
Unit
Min.
Null
value
value
V
−0.5
0
V
−10.5
−10.0
0
0
3.6
4.0
V
+10.5
+10.0
V
+10.5
+10.0
20.4
20.0
20.4
20.0
Linear transducer
Adapter cable with connector
(socket)
Indication
Indication
for
for teach-in
adjustment
2.0
4.0
2.0
4.0
6.0
12.0
6.0
12.0
2.0
4.0
2.0
4.0
6.0
12.0
6.0
12.0
Values for null and end point
-
Any desired position of the magnet can be used as the
null or end point. However, the null and end points may
not be reversed.
-
The absolute null and end points must lie within the
minimum or maximum range of what can be output
(see value table).
The last set values are always saved, regardless
of whether the setting was ended using the
programming inputs or automatically after
10 min have expired.
Value table for teach-in and inverting
The following examples refer to transducers
with 0 to 10 V or 4 to 20 mA output.
Calibration box
8-pin
Ignition protection
"ec" and "tb"
End
Max.
Error
value
value
value
+10.0
+10.5
+10.5
+10.0
+10.5
+10.5
20.0
20.4
20.4
20.0
20.4
3.6
0
−0.5
−0.5
−10.0
−10.5
−10.5
0
0
20.4
4.0
3.6
3.6
Supply