Connecting Sensors (Pnp Inputs) - Festo CPV GE ASI-8E8A-Z M8 Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 31

3.5 Connecting sensors (PNP inputs)

Use cable type KM8−M8−GSGD−... and plug with union nut
and M8x1 thread for connecting sensors.
Fasten the plugs/sockets with the aid of the union nut in
order to prevent unintentional loosening, e.g. due to
shock. Seal unused sensor connections with the protective
caps type ISK−M12 supplied. Only in this way can you com
ply with protection class IP65.
Please note
The inputs are protected against short circuit. In the
event of a short circuit the slave will be switched off.
The AS−Interface master regards this slave as faulty.
When the short circuit is eliminated, the slave responds
immediately as being functionable.
1
Inputs of the
first slave
2
Inputs of the
second slave
3
Pin assignment:
1: 24 V
3: 0 V
4: Input Ix
Festo CPV..−GE−ASI−8E8A−Z M8 0306c English
0
1
2
3
4
5
6
1
2
7
4
3
1
3
25

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cpv ge serieCpv ge-asi-8e8a-z m serie

Tabla de contenido