USERS MANUAL SOLADIN 600
Choosing the location to install
Obey the following stipulations during installation:
• The Soladin is suited for indoor use only.
• Ambient temperature: -20 ... 50°C; (power
derating above 40°C), Humidity: 0-90% non
condensing
• Install the Soladin in the vicinity of a wall socket
• Do not install the Soladin in environments with
heavy dust development or humidity.
• If the Soladin is installed in the immediate vicinity
of living areas, take into account that it produces
a slight noise level when operating.
• Mount the Soladin vertically on a solid, non-
resonating, wall.
• Mount the Soladin in such a way that obstruction
of the airflow through the ventilation openings is
prevented
• No objects must be located within a distance of
20 cm around the Soladin.
• Multiple Soladins must be mounted next to each
other, not above each other. Minimum spacing:
20 cm.
Part
Description
number
130000600
Soladin 600 230V/50Hz QNS - EU
130000610
Soladin 600 230V/50Hz QNS - IT
130000620
Soladin 600 230V/50Hz QNS - ES
130000630
Soladin 600 230V/50Hz QNS - UK
Table 1
Directions for installation
The Soladin is equipped with a so called "anti-
islanding safety device". It ensures immediate
switch off in case of grid failure. European countries
maintain different regulations with regard to anti-
islanding devices and the supply of energy back to
the utility grid in general. Check from the part
number on the type number plate whether the
version of the Soladin is appropriate to be
connected to the local utility grid. Refer to table 1.
Never connect the Soladin to a utility grid which is
not suitable for the use of the apparatus!
In the Netherlands only one Soladin may be
connected to an existing electricity branch circuit
which is fused with 16 Amp. In other countries
different restrictions apply. Please acquaint yourself
with the local regulations on this issue.
During installation you can check by means of the
LED-indicator whether the installation is done
properly. This check can only be carried out when
sufficient irradiation is present. Installation should
therefore be carried out during daytime only.
Although the Soladin is protected against wrong
polarity, the positive (+) and negative (–) of the solar
connections should not be exchanged.
Install the product according to the instructions
stated on page 4 and 5.
Monitoring
The Soladin has a communication port that can be
connected to the COM-port (RS232) of a PC or
laptop. Use the optional "Mastervolt PC–link"
interface and cable to set up a connection.
Part number
Description
130391030
PC-link Soladin 600,
incl. communication cable, 2m
Allowed to be used in:
Europe, except Germany and the countries mentioned
below
Italy
Spain
England
ENGLISH