GB
environment, moisture can enter the element.
This should not be seen as a fault, but is
simply rectified by connecting the appliance
to the mains supply via a socket without a
safety cut-out, so that the moisture can be
driven out of the element. The drying time
can vary from a few hours to a few days.
As a preventive measure the unit should
occasionally be run for a short time when it is
not being used for extended periods of time.
Safety
• Keep the areas around the air intake
and exhaust grilles free from possible
obstructions!
• During operation the surfaces of the unit
are hot!
• The unit must not be fully or partially
covered with textiles, or similar materials,
as overheating can result in a fire risk!
Technical specifications |
Type
Airflow
[m
/h]
3
AG4010A
1350/2030/2700
1900/2850/3800
AG4015A
AG4020A
2700/4050/5400
AG4025A
3150/4725/6300
Technical specifications |
Type
Output
stages
[kW]
AG4010E
0/ /10/15
AG4015E
0/ /15/22,5 1800/2700/3600 37/25/19
AG4020E
0/ /20/30
AG4025E
0/ /24/36
*
) Dt = Temperature rise of passing air at maximum heat output and low/medium/high airflow.
1
) Conditions: Distance to unit: 5 m. Direction factor: 2. Equivalent absorption area: 200 m. 2 .
*
2
Protection class AG4000A/E: (IP23).
16
AG 4000 A/E
Thermozone AG 4000 A
Sound level*
2
[dB(A)]
49/59/65
48/59/66
50/61/67
51/62/69
Thermozone AG 4000 E
Airflow
Dt*
1
[m
/h]
[
C]
3
°
1250/1880/2500 36/24/18
2600/3900/5200 34/23/17
3050/4575/6100 36/24/18
Voltage
Amperage
[V]
[A]
230V~
3,2
230V~
4,4
230V~
6,4
230V~
7,5
Sound
Voltage/
level*
amperage
2
[dB(A)]
(control)
49/59/65
230V~/3,2 A
48/59/66
230V~/4,4 A
50/61/67
230V~/6,4 A
51/62/69
230V~/7,5 A
Weight
[kg]
31
42
60
71
Voltage/
Weight
amperage
(heat)
[kg]
400V3~/22 A
39
400V3~/32,5 A
53
400V3~/43,5 A
76
400V3~/52,0 A
90

Publicidad