Mitsubishi Electric MXZ-8B48NA Manual De Instalación página 5

Ocultar thumbs Ver también para MXZ-8B48NA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Installation
location
............
'_,ii_i!;
_il "
: ,;,,. i o2,
_qi]
_hH_
V
(33
.... _ii
iiiiiiii;s _
; 03
(inch)
Fig. 3-5
Fig. 3-6
Fig. 3-7
Fig. 3-8
Fig. 3-9
Fig. 3-10
Fig. 3-12
Fig. 3-13
Fig. 3-14
Fig. 3-11
Fig. 3-15
Fig. 3-16
Fig. 3-17
3.4.2. When installing a single outdoor unit
Minimum
dimensions
are
as follows,
except
for
Max.,
meaning
Maximum
dimen-
sions,
indicated.
Refer
to the figures
for each
case.
d_ Obstacles
at rear only
(Fig.
3-5)
@)Obstacles
at rear and
above
only
(Fig.
3-6)
®Obstacles
at rear and
sides
only
(Fig.
3-7)
(4_Obstacles
at front
only
(Fig.
3-8)
,: When using the optional
air outlet guides, the clearance
is 19-11/16"
(500 mm) or more.
@Obstacles
at front
and
rear only
(Fig.
3-9)
,: When using the optional
air outlet guides, the clearance
is 19-11/16"
(500 mm) or more.
®Obstacles
at rear,
sides,
and above
only
(Fig.
3-10)
• Do not install the optional
air outlet guides for upward airflow.
3.4.3. When installing
multiple outdoor
units
Leave
3/8"
(10 mm)
space
or more
between
the units.
(DObstacles
at rear only
(Fig,
8-11 )
QObstacles
at rear and
above
only
(Fig.
3-12)
• No more than 3 units must be installed
side by side. tn addition, leave space as shown,
• Do not install the optionat air outlet guides
for upward airflow.
G Obstacles
at front
only
(Fig.
3-13)
,_ When using the optional
air outlet guides, the clearance
is 39-3/8" (1000 mm) or more,
_Obstacles
at front
and
rear only
(Fig,
3-14)
When using the optional
air outlet guides, the clearance
is 39-3/8" (1000 mm) or more.
(_ Single
parallel
unit arrangement
(Fig,
3-15)
,: When
using the optional
air outlet
guides
installed
for upward
airflow,
the clearance
is
39-3/8" (1000 mm) or more.
@Multiple
parallel
unit arrangement
(Fig.
3-16)
,: When using the optional
air outlet
guides
installed
for upward
airflow,
the clearance
is
59-1/16"
(1500 mm) or more,
(_ Stacked
unit
arrangement
(Fig.
3-17)
• The units can be stacked up to 2 units high.
• No more than 2 stacked
units must be installed
side
by side, tn addition, leave space
as
shown.