5. Installing
the refrigerant
piping
5.3. Addition of refrigerant
* When the unit is stopped, charge the unit with the additional
refrigerant
through
the liquid stop valve after the pipe extensions
and indoor unit have been vacu-
umized.
When the unit is operating,
add refrigerant
to the gas check valve using a safe-
ty charger. Do not add liquid refrigerant directly to the check valve.
Refer to the "1.5. Using R410A refrigerant
air conditioners"
for more information.
Table 1
Total piping length
41-50m
51-70m
71-90m
91-115m
bl+b2+al
+a2+a3+a4+a5+a6+a7+a8
(135-164ft.) (165-230ft.) (231-295ft.) (296-377ft.)
Additional
refrigerant charging amount
0.6 kg
1.4 kg
2.2 kg
3.2 kg
(21 oz)
(49 oz)
(78 oz)
(113 oz)
If connecting
an indoor unit with _9.52 mm (3/8 inch) liquid pipes (model number
24 or more for M- and S-Series and model number 18 or more for P-Series'_. the
additional
refrigerant
charging amount in Table 1 must be corrected (add the follow-
ing AR value from the value given in Table 1 ).
Additional
refrigerant
charging correction
amount
AR = 0.01 [kg/m] x _9.52 (3/8 inch) branch pipe (liquid pipe) total length [m]
(0.107 [oz/ft] x _a9.52 (3/8 inch) branch pipe (liquid pipe) total length [ft])
Example)
bl = 20 m (66 ft.). b2 = 25 m (82 ft.)
Indoor unitA
_9.52 (3/8) Liquid pipe
a1=12 m (39 ft.)
Indoor unit B
_6.35 (1/4) Liquid pipe
a2=11 m (36 ft.)
Indoor unit C
_6.35 (1/4) Liquid pipe
a6=14 m (46 ft.)
Indoor unit D
_9.52 (3/8) Liquid pipe
a7=13 m (43 ft.)
Total piping length : b1+b2+a1+a2+a6+a7=95
m (312 ft.)
--_ According to Table 1, the additional refrigerant charging amount is 3.2 kg (113 oz).
Because indoor units with _a9.52 (3/8) liquid pipes are connected
(indoor units A and
D in this example), the additional
refrigerant charging amount must be corrected.
Additional
refrigerant
charging correction
amount
AR = 0.01 [kg/m] x _9.52 (3/8) branch pipe (liquid pipe) total length (al +a7)
= 0.01 x (12+13 m) [0.107 x(39+43 ft.)]
= 0.25 kg (9 oz)
Therefore
the additional
refri(]erant
charaina amount is
3.2 kg + 0.25 kg = 3.45 kg [113 oz + 9 oz =122 oz].
• in case of using 1-branch
box
Flare connection employed. (No. brazing)
Branch box
0
• in case of using 2-branch
boxes
2 branches
pipe (joint)
(1) Valve size for outdoor unit
(2) Valve size for branch
box
Branch box #2
Fig. 5-2
mm (3/8 inch)
__)
Liquid pipe
_a6.35 mm (1/4 inch)
A_ UNIT
Gas pipe
_a9.52 mm (3/8 inch)
Liquid pipe
_a6.35 mm (1/4 inch)
a_ UNIT
Gas pipe
_a9.52 mm (3/8 inch)
Liquid pipe
_a6.35 mm (1/4 inch)
UNIT
Gas pipe
_a9.52 mm (3/8 inch)
Liquid pipe
_a6.35 mm (1/4 inch)
UNIT
Gas pipe
_a9.52 mm (3/8 inch)
Liquid pipe
_a6.35 mm (1/4 inch)
UNIT
Gas pipe
_a12.7 mm (1/2 inch)
* 3-branch type : only [A],1_. [] unit
Conversion
formula
/('_'_
f--'_
_B_
1/4 F
_6.35 (1/4)
3/8 F
_9.52 (3/8)
1/2 F
_12.7 (1/2)
5/8 F
_15.88 (5/8)
r,u'-:-.
5-3
3/4 F
_19.05 (3/4)
t
5.4. Selecting pipe size (Fig. 5-2)
Conversion
formula
The piping connection size differs ac-
_9.52 mm
cording to the type and capacity of indoor
Liquid
units. Match the piping connection
size of
(3/8 inch)
branch box with indoor unit.
If the piping connection
size of branch
box does not match the piping connection
size of indoor unit, use optional
different-
_15.88 mm
Gas
diameter (deformed)
joints to the branch
(5/8 inch)
box side. (Connect deformed joint directly
to the branch box side.)
Different-diameter
joint (optional
parts) (Fig. 5-3)
iiiiiiii
MAC-A454JP
_a9.52 (3/8) --_ _a12.7 (1/2)
_9.52 (3/8)
_a12.7 (1/2)
MAC-A455JP
_a12.7 (1/2) --_ _a9.52 (3/8)
_12.7 (1/2)
_a9.52 (3/8)
MAC-A456JP
_a12.7 (1/2) --_ _a15.88 (5/8)
_12.7 (1/2)
_a15.88 (5/8)
PAC-493PI
_a6.35 (1/4) --_ _a9.52 (3/8)
_6.35 (1/4)
_a9.52 (3/8)
PAC-SG78RJ-E
_a9.52 (3/8) --_ _a15.88 (5/8)
_9.52 (3/8)
_a15.88 (5/8)
Piping preparation
Table below shows the specifications
of pipes commercially
available.
: i_i_
6.35 (1/4)
8 (5/16)
9.52 (3/8)
8 (5/16)
Heat resisting foam plastic 0.045
12.7 (1/2)
8 (5/16)
specific gravity
15.88 (5/8)
8 (5/16)
) Ensure that the 2 refrigerant
pipes are insulated to prevent condensation.
Refrigerant
pipe bending radius must be 4" (100 ram) or more.
z_ Caution
Be sure to use the insulation
of specified
thickness.
Excessive
thickness
may cause incorrect
installation
of the indoor
unit and branch
box, and
lack of thickness
may cause dew drippage.
2-branch
pipe (Joint) : Optional
parts (According
to the connection
method,
you can choose the favorite
one.
MSDD-50AR-E
flare
MSDD-50BR-E
brazing
installation
procedure
(2 branches pipe (Joint))
Refer to the installation
manuals of MSDD-50AR-E
and MSDD-50BR-E.
7