"Level" Installation; Installation For Level - Siemens SITRANS P500 Instrucciones De Operación

Ocultar thumbs Ver también para SITRANS P500:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 98
Figure 3-2
Fastening the pressure transmitter on the mounting bracket with vertical differential pressure lines
3.4

"Level" installation

3.4.1

Installation for level

Note
Seals are required for the installation. The seals must be compatible with the medium to be measured.
Seals are not included in the delivery.
Procedure
To install the pressure transmitter for level, proceed as follows:
1. Attach the seal to the container's mating flange.
Ensure that the seal is centrically positioned and that it does not restrict the movement of the flange's seal diaphragm in
any way as otherwise the tightness of the process connection is not guaranteed.
2. Screw on the pressure transmitter's flange.
3. Observe the installation position.
SITRANS P500 with HART
A5E02344532-04, 12/2014
13

Publicidad

Tabla de contenido
loading

Tabla de contenido