5.3.2
Commissioning in gaseous environments
Usual arrangement
①
Pressure transmitter
②
Stabilizing valve
③
④
Differential pressure valves
,
⑤
Differential pressure lines
Pressure transmitter above the differential pressure
transducer
Prerequisite
All shut-off valves are closed.
Procedure
To commission the pressure transmitter for gases, proceed as follows:
1. Open both the shut-off valves
2. Open the stabilizing valve
3. Open the differential pressure valve (
4. Check and if required correct the zero point when the start of scale value is 0 mbar (4 mA).
5. Close the stabilizing valve