RISK OF FIRE OR ELECTRIC SHOCK
Read all of these assembly directions BEFORE beginning installation.
This system must be installed by qualified personnel in accordance
with local codes.
• Before drilling holes to anchor Thread to building floor, verify floor does NOT contain hidden electrical wiring, structural cabling,
radiant heat systems, or other obstructions. Consult with the building's architect or Engineer of Record to plan accordingly.
• Only connect this system to a dedicated 120-127 V~ 60Hz 20A single phase GFCI protected building power circuit
(bare copper or green
wire is ground, white wire is neutral, and black wire is hot).
• The building electrical supply connection must be performed by a licensed electrician.
• Inspect all parts of system before installation to ensure there is no damage to any of the parts. Do not use the Power Track Infeed or
Power Track if they are damaged during handling or are damaged in the installed position. All damaged parts must be replaced
before installation.
• Only install and use this system on sub-floors made of concrete or wood that are prepared as follows:
• Remove all high points or bumps taller than 1/8 inch in the sub-floor along the installation path.
• Abrupt height changes greater than 1/8 inch must be filled in and gradually ramped over a distance of 12 inches.
• Within 9 inches from the center of a connector, the sub floor must be flat within 1/16 inch.
• Holes equal to or greater than 1 inch across must be filled with floor patch and sanded down to the main floor surface.
• Ensure all debris is removed from the installation path.
• (For floor infeed) Flush mounted box must be within 1/16 inch of flush to adjacent floor.
• Only install and use this system indoors in dry locations.
• To prevent liquids from entering product, connect or cap each receptacle opening per these Assembly Directions.
• To prevent liquids from entering product, assemble the floor infeed per these Assembly Directions.