Optional Installation
2
Relay Contact-Closure Connection
Use the included DB9 cable (see
cialized electronic equipment to the relay contact-clo-
sure port on your UPS System. See diagram
chart below to determine signals carried by this port.
Relay Contact Closure Chart
Line Fail
Indication
UPS Operating
Pins 1
Conditions
& 6
AC Input Voltage OK
CLOSED
AC Input Out of Range
OPEN
Battery More than 3 Min.
Remaining Charge*
Battery Less than 3 Min.
Remaining Charge*
Battery More than 2 Min.
Remaining Charge*
Battery Less than 2 Min.
Remaining Charge*
Open on
Line
Contact Action
Failure
* Times are approximate, at full load.
EPO Port Connection
3
This optional feature is only for those applications
which require connection to a facility's Emergency
Power Off (EPO) circuit. When the UPS is connected
to this circuit, it enables emergency shutdown of the
UPS's inverter.
Using the cable provided, connect the EPO port of
your UPS (see
3a
normally open switch according to the circuit diagram
(see
). The EPO port is not a phone line surge sup-
3b
pressor; do not connect a phone line to this port.
4

External Battery Connection

All UPS models come with a robust internal battery
system; select models feature connectors (see
accept optional external battery packs (sold separately
from Tripp Lite) to provide additional runtime. Adding
external batteries will increase recharge time as well as
runtime. See battery pack owner's manual for complete
installation instructions. Make sure cables are fully
inserted into their connectors. Small sparks may result
during battery connection; this is normal. Do not connect
or disconnect battery packs when the UPS is running
on battery power.
If you connect any external batteries, set the Battery
Charge Level Switch (see
This will increase your UPS's charger output so the addi-
tional batteries charge faster. Note: the switch to the right
of the Battery Charge Level Switch is inactive and will
not affect UPS operation regardless of its position.
CAUTION! DO NOT set the Battery Charge Level Switch to the
down position without an external battery connected. There is a risk
of damaging the UPS's internal battery system.
8/8/2008
continued
) to connect spe-
2a
Mid Battery
Low Battery
Indication
Indication
Pins 2
Pins 7
Pins 8
Pins 4
& 6
& 3
& 3
& 9
OPEN
CLOSED
OPEN
CLOSED
CLOSED
OPEN
OPEN
CLOSED
Close on
Close
Open
Close
Line
Below
Below
Below
Failure
Mid
Mid
Low
Battery
Battery
Battery
Battery
) to a user-supplied normally closed or
) to the down position.
4b
6
10:10 AM
Page 6
and
2b
2a
Pins 5
& 9
NO TE :
TOP OF DUAL
DB9 (J5/J34)
J5
REMOTE CONTACTS
1
K1 A
CLOSED
LINE FAIL
2
OPEN
K4 A
3
MID BAT
Open
Below
4
Mid
K1 0A
Battery
LO BATT
5
2b
3a
) that
4a
3b
4a
4b
OPENS ON LINE FA IL
6
COM
CLOSE S ON LINE FAIL
7
CLOSES BELOW MID BAT TERY
COM
8
OPENS BELOW MID BATTERY
CLOSES BELOW LOW BATTER Y
9
COM
OPENS BELOW LOW BATTERY
4-5