External Battery Cabinet Connection; Cold Start - Tripp-Lite SmartOnline SV Serie Manual Del Propietário

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7. Installation

7.2.5 External Battery Cabinet Connection

Once the battery installation is completed, ensure the corrected nominal battery voltage (+/- 120V DC), battery capacity and maximum charging
current data is programmed into the LCD settings. If the actual installation settings differ from the default settings in the LCD, the UPS alarm may
sound continuously. See Section 9.3.6.3: Battery for details.
Once all modules are assembled and installation cabling is complete, switch the UPS main breaker on the front of the UPS to "On". The UPS
system is now on bypass. Enter the Controls Screen on the Control Panel to place the UPS system in full operation. See Section 9.3.4 Control
Screen for details.

7.3 Cold Start

Start Up of the UPS System should be undertaken via the Control Panel. It is possible to start the UPS without an AC input via the "Cold Start"
button on the Power Module:
1. Press the "Cold Start" button as shown in the figure below.
2. The UPS will enter standby mode. Immediately press the "Power On/Off" button and hold for 2 seconds, and the UPS will enter Battery Mode.
The Inverter and Battery LEDs will be illuminated. Cold Start procedure is complete.
If more than one Power Module is installed in the frame, performing the cold start procedure on one will translate to all other Power Modules
installed automatically.
Note: The UPS system will function correctly upon initial startup. However, maximum system battery runtime will be available only after the UPS system has been
charged for approximately 24 hours.
External battery
cabinet
External battery
cabinet
Back panel of Switch Unit
+
N
-
External
Battery
Input/Output
Breaker and
Disconnect
+
-
N
Figure 7.4
Figure 7.5
17
Cold Start Button
POWER

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido