COMBUSTION AIR REGULATION
The air gate is regulated by the motor reducer.
The regulation of open/closed and 1st flame/max open positions is obtained by tur-
ning the cams counter-clockwise to increase the opening of the gate, and clockwise
to reduce it. Push button B to disengage the gate traction system, therefore making
manual movement possible.
Cam I
maximum air opening
Cam II
air closure, while still
Cam III
air opening, 1st stage ignition
Cam IV
consent for the opening of 2nd stage valve
(at least 6o more than cam III)
HYDRAULIC CONNECTIONS AND PUMP PRESSURE REGULATION
The pump is regulated at the factory at 22 bar. For pressure control, use an oil manometer. Pressure can be regulated
within 22 and 26 bar.
SUNTEC pump type E...
1
3
4
CAPTION
1 Vacuum meter suction or attachment – ½"
2 Return and internal by-pass grub screw – ½"
3 Outlet to nozzle – ¼"
4 Pressure manometer attachment – 1/8"
5 Pre-heater cavity
6 Pressure regulation
TECHNICAL NOTE REGARDING "ECO DEN" LOW-SULPHUR COMBUSTION OIL
ECO DEN fuel has low sulphur contents (≤ 0.5% in weight) and can therefore be considered an environmentally-friendly
fuel, with emissions of sulphur dioxide (SO
12-15° E at 50° C does not normally consent direct suction from the tank by means of the burner pump. In such cases it is
advisable to provide a "ring" supply circuit for the burner with an auxiliary pump which will make fuel circulate and supply
the burner itself.
1
3
5
5
4
6
1
2
Legenda
1 Suction – ¼"
2 Return – ¼"
3 Outlet to nozzle – 1/8"
4 Pressure manometer attachment – 1/8"
5 Vacuum meter attachment – 1/8"
6 Pressure regulation
) and sulphur trioxide (SO
2
- 30
-
SUNTEC pump type D...
) similar to those of diesel. Its nominal viscosity of