Safety instructions

WARNING
Risk of injury when operating with open
housing!
Close housing after maintenance!
• Be calm and focused and ensure proper
operation.
• Protect yourself and other persons, ani-
mals, property, and the environment by
taking the necessary protective measures
and being trained in use of the devices to
prevent harm to your health, property
damage,
financial
harm or risk of accident.
• Repairs may be carried out only by
Schneider Druckluft GmbH or its approved
service partners.
• Intervention in the cooling circuit: only
qualified personnel from Schneider Druck-
luft GmbH permitted during the warranty
period, qualified experts as specified in
DIN EN 378 permitted after the warranty
expires.
• When a leak in the cooling circuit is re-
paired, a leak inspection should be carried
out within one month of the repair as spec-
ified in EC Regulation 842/2006.
• Handling HFCs: observe BGI 648 or appli-
cable national regulations!
• Condensate disposal: observe Water Re-
sources Act (WRA) regulations or national
regulations!
• Prohibited: manipulation, inappropriate
use, temporary repairs, use of other ener-
gy sources, removal or use of damaged
safety equipment, operating a malfunc-
tioning or leaking system, use of non-orig-
inal spare parts, transporting, maintaining,
repairing, leaving a pressurised machine
unattended, smoking, naked flames, re-
moving stickers.
7

Components

01 Compressed air outlet
02 Compressed air inlet
03 ON/OFF switch
07 Plate heat exchanger
08 Hot gas bypass valve
09 Condensate discharger (float diverter)
loss,
environmental
10 Refrigerant compressor
11 Condensate outlet
12 Capillary pipe
13 Refrigerant filter dryer
14 Refrigerant condensator
15 Ventilator motor
16 Ventilator
17 ECO controller/switch
See Fig. 1a
8

Commissioning

Observe the safety instructions!
8.1
Transport
• Depressurise compressed air cold dryer
and place in vertical position prior to trans-
porting
8.2
Installation
Conditions at the installation location
• Rooms: as dust-free as possible, dry, well
ventilated.
Assembly
• Maintain 50 cm of clearance space around
the compressed air cold dryer to allow
maintenance, sufficient ventilation and
correct functioning of the unit.
• Mount the compressed air cold dryer or in-
stallation equipment designed to withstand
to the weight load of the compressed air
cold dryer to a wall.
• Mount the compressed air cold dryer using
the two keyholes on the back of the unit
and hook screws with a minimum diameter
of 10 mm, for example.
• Pipelines in the direct vicinity of the com-
pressed air cold dryer must be secured at
a minimum of one fixed attachment point.
• Never use the compressed air cold dryer as
a means of supporting pipelines.
• Make sure that the compressed air cold
dryer does not cause vibrations in the pipe-
line system.
• We recommend installing a bypass line to
perform maintenance without interrupting
operation.
• When assembling the inlet and outlet lines,
hold the connection on the compressed air
cold dryer using a suitable tool to prevent
it from rotating!
• Do not use conical threads or connections.
DK 600 - 3500 ECO