Purchased parts package

Calculator multidata WR3
Seal material
Wall holder with mounting accessories
Installation and operating manual

Technical Data Multidata WR3

Temperature range
Temperature difference
Display
Display unit
Interface flow sensor
Temperature sensor
connection
Max. cable length 2-wire
Max. cable length 4-wire
Interface
Ambient temperature
Power supply
Battery lifetime
Protection class
Mechanical/electro-mag-
netic class
Accuracy class
Measuring cycle dynamic
(*) Possibility for battery replacement is depending on the country, please check the relevant
national regulations
Check the contents of the packa-
ge before installation to be com-
plete.
°C
k
Multifunctional LCD, 8-digit, floating
MWh, kWh, GJ, MJ
Models with contac pulsers or active pulser
(no Namur or Opto),
passive max. 1 Hz/ active max. 100 Hz
PT500, optional PT100, PT1000
m
m
optical, optionally: M-Bus,
remote readout outputs
°C
3,6 V Lithium battery; extern with M-Bus,
optionally power supply (230V/24V)
>6 years, optionally >11 years
(changeable during the operation) (*)
IP 54 / IP 65, according to DIN 40050
according to EN1434
0 - 150
3 - 120
12,5m (PT500),
2,5m (PT100),
20m (PT1000)
20m
5 - 55
M1 / E1
40s / 30s / 10s