Status Display / Error Codes - Zenner MULTIDATA WR3 Manual De Instalacion Y Uso

Unidad digital para contadores de energía para calorías y/o frigorías con 2 entradas/salidas configurables de pulsos y opcionalmente comunicación m-bus, rs-232, rs-485
Ocultar thumbs Ver también para MULTIDATA WR3:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Español
Italiano

Status display / Error codes

The symbols in the table below show the meter's operational status.
The status messages only appear in the main display (energy). The
temporary display of the warning triangle can be caused by special
operating states and does not always mean that the device is malfunc-
tioning. However, should the symbol be displayed over a longer period
of time you should contact the service company.
Symbol
Status
External voltage
Flow existent
Attention!
Symbol flashing:
Data transmission
Symbol constantly displayer:
optical interface active
Emergency operation
Code
Error
1
Short-circuit return sensor
2
Interruption return sensor
3
Short-circuit supply sensor
4
Interruption supply sensor
5
Hardware error
Battery empty or wrong temp.
6
Sensor
Temperatures out of measuring
7
range
100
Emergency operation
Battery life time exceed
1000
Initial verification expired
2000
> 8000 Internal hardware error
Error codes show faults detected by multidata. If more than one error
appears, the sum of the error codes is displayed: Error 1005 = error
1000 and error 5.
Measure
-
-
Check system /device for errors
-
-
Exchange device
Measure
Check sensors, replace if needed
Check sensors, replace if needed
Check sensors, replace if needed
Check sensors, replace if needed
Exchange device
Check device / sensor
Correction heating system
Exchange device
Exchange device
Exchange device
Exchange device
25

Publicidad

Tabla de contenido
loading

Tabla de contenido