7. Configuration
7. Configuration
Configuration is carried out using a USB interface with a PC via the model PU-548
programming unit (accessories, order number: 14231581). The connection with the
EN
thermometer is made via the appropriate adapter cable (accessories: M12 x 1 circular
connector, order number: 14003193).
Measuring range, damping, error signalling, Tag No. and other parameters can be adjusted
(see configuration software).
The measuring range is configurable between -50 ... +250 °C [-58 ... +482 °F]. The
configuration software checks the required measuring range and will only accept
permissible values. Intermediate values are configurable - the smallest increment is 0.1 °C
or 0.1 °F. The thermometers are delivered configured to customer specifications within the
configurable limits.
Please note:
The measuring range of the thermometer is limited by the application range of the
measuring element, not by the setting range of the transmitter.
Maximum permissible temperatures:
At the case with transmitter: 85 °C [185 °F]
■
Temperature at the connector: max. 85 °C [185 °F]
■
Model TR21-A:
■
-30 ... +250 °C [-22 ... +482 °F]
Model TR21-B:
■
-30 ... +150 °C [-22 ... +302 °F]
Model TR21-C:
■
-30 ... +150 °C [-22 ... +302 °F]
-30 ... +250 °C [-22 ... +482 °F]
16
Easy to use
■
LED status display
■
Compact design
■
No further power supply is needed for either the
■
programming unit or for the transmitter
(replaces programming unit model PU-448)