Festo VPPM C1 Serie Manual Del Usuario página 14

Ocultar thumbs Ver también para VPPM C1 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
6.5 Configuring the VPPM-...C1
Editing the pressure range and the arrangement of the setpoint value display
1. In order to activate the EDIT mode, press the EDIT key.
Only with active security locking - [lock] flashes:
2. Press the UP/DOWN key until the desired security code is set and confirm by pressing the EDIT
key.
[Out] flashes.
3. Press the UP/DOWN key until [In] flashes in the display, then press the EDIT key.
[min] flashes.
Editing the pressure regulation range:
4. Set the minimum pressure value with the UP/DOWN keys, then press the EDIT key.
[max] flashes.
5. Set the maximum pressure value with the UP/DOWN keys, then press the EDIT key.
The current setpoint value display type flashes.
– Either [mA] or [V] flashes, depending on the variant of the VPPM-...C1
– or percent [%] flashes
– or [kPa], [psi] or [bar] flash, depending on the unit set in the SPEC menu.
Configuring the setpoint value display
6. Set the desired display type using the UP/DOWN keys, then press the EDIT key.
The VPPM-...C1 is in the RUN mode again.
Fig. 21
Configuring the switching output (Out)
Warning
Depending on the functions of the machine/system, the manipulation of signal
statuses can cause serious injury to people or material damage.
• Note that changing the switching characteristics of the switching outputs in
the EDIT mode is effective immediately.
• Define the desired switching characteristics of switching output D3.
Switching points (SP...) and hysteresis (Hy)
With setting SP.O.
p [bar]
U [V]
Fig. 22
Switching points (SP...) and hysteresis (Hy) with NO setting (normally open
contact)
OUT
With threshold
comparator setting
1
0
With window
OUT
comparator setting
1
0
Fig. 23
Hysteresis
Setpoint value
Actual value
SP.O. signal
Hy
SP
Hy
Hy
SP
SP
min
max
Switching points (SP...) and hysteresis (Hy) with NO setting (normally open
contact)
With threshold
comparator setting
With window
comparator setting
Fig. 24
Configuring the switching output
1. In order to activate the EDIT mode, press the EDIT key.
Only with active security locking: [Lock] flashes
2. Press the UP/DOWN key until the desired security code is set and confirm by pressing the EDIT
key.
[Out] flashes.
3. Press the EDIT key.
The current switching reaction flashes.
4. Select the desired switching characteristic (threshold value/window comparator or S.O.) with
the UP/DOWN key and confirm with the EDIT key.
With threshold value/window comparator switching function:
[SP] or [SP] [
] flashes.
min
5. Set the switching point (SP or SP
With window comparator switching function:
[SP] [
] flashes.
max
6. Set the switching point (SP or SP
[Hy] flashes.
7. Set the hysteresis (HY) with the UP/DOWN key and confirm with the EDIT key.
[NO] or [NC] flashes.
t
8. Set the switching characteristic (NO/NC) with the UP/DOWN key and confirm with the EDIT key.
The VPPM-...C1 is in the RUN mode again.
Fig. 25
t
Forcing the input
1. In order to activate the EDIT mode, press the EDIT key.
Only with active security locking: [Lock] flashes
2. Press the UP/DOWN key until the desired security code is set and confirm by pressing the EDIT
key.
[Out] flashes.
3. Press the UP/DOWN key until [Force] flashes in the display, then press the EDIT key.
4. [Force] flashes.
5. The set value can now be edited by pressing the UP and DOWN keys.
Caution
The new specified value will be accepted immediately by the controller.
6. By pressing the EDIT button, you can exit the Force mode. The analogue voltage and current
values of the input still apply.
The VPPM-...C1 is in the RUN mode again.
Fig. 26
P
P
OUT
1
Hy
0
OUT
1
Hy
0
SP min
) with the UP/DOWN key and confirm with the EDIT key.
min
) with the UP/DOWN key and confirm with the EDIT key.
max
P
SP
Hy
P
SP max

Publicidad

Tabla de contenido
loading

Tabla de contenido