Preparing For Commissioning; Fast Commissioning With Factory Setting - Festo VPPM C1 Serie Manual Del Usuario

Ocultar thumbs Ver también para VPPM C1 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
Note
If the Y-connecting cable type NEBV-M12G8-KD-...-M12G5 is connected to CPX
I/O modules, galvanic separation of the I/O modules is no longer guaranteed!
• Connect the VPPM-...C1 as shown in the corresponding port pattern:
Connection patterns VPPM-...C1
Voltage variant
(type VPPM-...-V1...C1)
PIN
2
U
v
D3
out
8
0...10 V
4
W+
W-
3
6
X
GND
7
1
D1
ext in
Fig. 13
The individual pins on the electrical connection are assigned as follows:
PIN Cable
Port identifications
1)
colour
Voltage variant
type
VPPM-...-V1...C1
1
White
Digital input D1
(WH)
2
Brown
+24 V DC supply voltage
(BN)
3
Green
Analogue input W- (- setpoint value)
(GN)
4
Yellow
Analogue input W+
(YE)
(+ setpoint value)
0 ... 10 V
5
Grey (GY)
Digital input D2
6
Pink (PK)
Analogue output X (actual value)
7
Blue (BU)
GND supply earth
2)
8
Red (RD)
Digital output D3
PE braided screen on thread
1)
Using the plug socket with cable as specified in Accessories. The maximum tightening torque is
0.5 Nm
Fig. 14
Circuit diagrams for VPPM-... switching output
PNP
2
BN
P
+24 V
RD
8
R
L
0 V
BU
7
PNP
Fig. 15
6
Commissioning

6.1 Fast commissioning with factory setting

The VPPM-...C1 is delivered with the following factory setting:
– Switching characteristics:
– Switching point:
The switching point is only active when a comparator is active (threshold value
or window comparator).
– Hysteresis:
– Switching characteristic:
If you wish to use the factory setting but define a different switching point for Out,
proceed as follows;
Note
When the operating voltage is switched on, the VPPM-...C1 is automatically in
the RUN mode (basic setting). If you are not sure whether the VPPM-...C1 is in
the RUN mode, hold the EDIT button down for 3 seconds. The VPPM-...C1 is then
in the RUN mode. You can set switching points manually.
You can set a switching point manually as follows:
1. In order to activate the EDIT mode, press the EDIT key.
è [Out] flashes.
Current variant
(type VPPM-...-A4...C1)
PIN
2
U
v
8
D3
out
4...20 mA
4
w+
w-
3
6
X
GND
A
7
5
D2
ext in
M12 plug connector
Current variant
type
VPPM-...-A4...C1
2
3
Analogue input W+
(+ setpoint value)
4 ... 20 mA
4
NPN
2
BN
P
RD
8
R
7
BU
NPN
threshold value comparator
40 % FS (Full Scale)
0.5 % FS
NO (normally open – N/O contact)
2. Press the EDIT key twice.
è SP flashes.
3. Modify the threshold value shown with the UP or DOWN key.
4. Hold the EDIT key pressed down for 3 seconds.
è The VPPM-...C1 is in the RUN mode.

6.2 Preparing for commissioning

Note
• Make sure that the VPPM-...C1 is kept away from high-frequency radiation
(e.g. from radio sets, mobile telephones or other interference-emitting devi­
ces). In this way you will avoid increased tolerances of the outlet pressure
(specifications for EMC è Technical data).
• The VPPM-...C1 interprets setpoint value signals which are smaller than 1 % of
full scale as 0 V (è Fig. 29). In this case, the working pressure will be set to
the ambient pressure.
During initial start-up, the RUN mode appears. This shows the current measured
value. By briefly pressing the DOWN key, you can display the setpoint value.
The RUN mode can be accessed from other modes:
1
5
D1
– Press EDIT key for 3 seconds.
D2
– When a monitoring period expires (timeout è Menu structure section)
ext in
ext in
Proceed with preparation for commissioning as follows:
• Switch on the operating voltage.
è The VPPM-...-C1 is in the RUN mode.
• Check functions of the VPPM-...C1.
Observe the following when setting the control characteristics via digital inputs or
display:
Note
8
1
Selection of the control characteristics via the digital inputs D1 and D2 takes
priority over the factory parameter sets in VPPM-...C1.
• When selecting the control characteristics via the factory parameters, make
sure that a logic 0 signal is present at digital inputs D1 and D2.
7
• You can select the desired factory parameter set in the EDIT menu on the
VPPM-...C1 (è Fig. 27). Parameter set [Set 2] (universal control characteri­
stics) is preselected at the factory.
5
6
• If you wish to preselect the control characteristics via the digital inputs D1 and
D2, create the following signals:
Parameter set
1
2
3
...
1) 1 = 24 V DC / 0 = 0 V DC
+24 V
Fig. 16
L
0 V
Control response
Fast control response
Universal control response
(factory setting)
Precise control reaction
Select the desired parameter set via
display of the VPPM-...C1
Input D1
Input D2
PIN 1
PIN 5
1)
1)
1
0
1)
1)
0
1
1)
1)
1
1
1)
1)
0
0