4.2
Basic drive functions
Set stop function
The standard stop (in the following called "stop") of the drive will be automatically activated by the internal state
machine if a basic function is deactivated and the drive is not yet at standstill.
Parameterising dialog ("Application parameter" tab):
Overview
Stop
Parameter list ("All parameters" tab):
Basic drive functions
LS_Stop
Software manual 9400 HighLine:
Basic drive functions
Stop
Set quick stop (QSP)
In contrast to the stop function, quick stop (QSP) is required for a stop in case of an error. If quick stop is activated,
the drive is braked to standstill irrespective of the defined setpoint within the deceleration time set for quick stop.
Parameterising dialog ("Application parameter" tab):
Overview
Quick stop
Parameter list ("All parameters" tab):
Basic drive functions
LS_Quick stop
Software manual 9400 HighLine:
Basic drive functions
Quick stop
Software limit positions / Set limitations for profile parameters
The basic function "Limiter" monitors the travel range limits via limit switches and parameterised software limit
positions and can lead the drive to defined limit ranges when being asked accordingly by the safety module.
Danger!
The safety is exclusively ensured by the safety module!
When the request for the safety function is cancelled, the drive restarts automatically.
Ensure by external measures that the drive only starts after a confirmation (EN 60204).
Note!
In order that the basic function "Limiter", after being asked accordingly by the safety module, can lead the
drive to the defined limit ranges before the limits set for the safety module are reached which stops the
drive, the limit values for the basic function "Limiter" must be set lower than the limit values for the safety
module!
Parameterising dialog ("Application parameter" tab):
Overview
All basic functions
Parameter list ("All parameters" tab):
Basic drive functions
LS_Limiter
Software manual 9400 HighLine:
Basic drive functions
Limiter
EDB94AXX6954 DE/EN/FR/ES/IT 4.0
Limiter
L
9400 HighLine | Commissioning guide
Extended commissioning
Basic drive functions
31