Terminal Assignment Of The Technology Applications; Actuating Drive - Speed; Actuating Drive - Torque - Lenze L-force 9400 Guía Para La Puesta En Marcha

Ocultar thumbs Ver también para L-force 9400:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

9400 HighLine | Commissioning guide

Terminal assignment of the technology applications

Actuating drive – speed
5
Terminal assignment of the technology applications
5.1
Actuating drive – speed
Terminal
X3
AI1-
AI1+
X5
RFR
DI1
DI2
DI3
DI4
DI5
DI6
5.2
Actuating drive – torque
Terminal
X3
AI1-
AI1+
AI2-
AI2+
X5
RFR
DI1
DI2
DI3
DI4
DI5
DI6
34
Assignment (Lenze setting)
Speed setpoint
• ±10 V ≡ ±100 % Motor reference speed (C00011)
Controller enable
Quick stop
Enable speed follower
Invert speed setpoint
Activate fixed setpoint 1 as speed setpoint
Reset error
Enable manual jog via DI7 and DI8:
DI7
DI8
Function
LOW
LOW
Stop
HIGH
LOW
Manual jog in positive direction
LOW
HIGH
Manual jog in negative direction
HIGH
HIGH
- (previous state remains unchanged)
Assignment (Lenze setting)
Torque setpoint
• ±10 V ≡ ±100 % Motor reference torque (C00057/2)
Speed limit value
• ±10 V ≡ ±100 % Motor reference speed (C00011)
Controller enable
Quick stop
Enable torque follower
Invert torque setpoint
Activate fixed setpoint 1 as speed limit value
Reset error
Enable manual jog via DI7 and DI8:
DI7
DI8
Function
LOW
LOW
Stop
HIGH
LOW
Manual jog in positive direction
LOW
HIGH
Manual jog in negative direction
HIGH
HIGH
- (previous state remains unchanged)
L
EDB94AXX6954 DE/EN/FR/ES/IT 4.0

Publicidad

Tabla de contenido
loading

Tabla de contenido