baltur BT 40 MG Instrucciones De Uso página 33

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

MAIN HYDRAULIC DIAGRAM TO FEED WITH PRESSURE SEVERAL
BURNERS AT TWO FLAMES OR MODULATING ONES OPERATING WITH
MAX NOMINAL VISCOSITY OF 5° E AT 50° C
The light oil recovery tanks (diameter ~ 150, height ~ 400)
should be installed as near as possible to the burner and should
be about 0,5 m. higher with respect to the burner's pump.
DRAWING (AS REFERENCE POINT)
SHOWING THE PLACING OF
NOZZLE - ELECTRODES - FLAME DISK
< 31 >
1 - Main tank
2 - Filter
3 - Circulation pump
4 - Water and plant discharge
5 - Air-gas discharge, normally closed
6 - Fuel and degasser recovery
7 - One-way valve
8 - By-pass (normally closed)
9 - Adjustable pressure regulator (0.2÷1 bar)
10 - Manometer (0÷4 bar)
N° 0002931451
data:13/01/2000
N° 0002901120
data:19/02/2002

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bt 55 mg

Tabla de contenido