TYPE OF PROBLEM
The unit reverts to flame lockout
(red light on)
The problems is limited to the
flame control device
The unit reverts to lockout,
spraying fuel without checking
for flame (Red light on)
The problem is limited to the
ignition device as long as the
fuel is in good condition (not
contamined with water or
anything else) and is adequately
atomized
The unit reverts to lockout,
spraying fuel without checking
for flame (Red light on)
The unit reverts to lockout
without spraying fuel (Red light
on)
Noisy burner pump
Burner does not start up
TROUBLESHOOTING FOR LIGHT OIL BURNERS
POSSIBLE CAUSE
1) Photoresistance is broken or fouled with
smoke
2) Insufficient draught
3) Photoresistance circuit failure
4) Fouled disk or opening
1) The ignition circuit is cut off
2) The ignition transformer wires are dried
out
3) The ignition transformer wires have not
been connected
4) Ignition transformer failure
5) The gap between the electrodes is not
correct
6) The electrodes discharge to ground
because they are fouled or because the
insulation is cracked; remember to check
under the clamps securing the insulation
1) Pump pressure is not uniform
2) There is water in the fuel
3) Excessive combustion air
4) The air passage between the disk and
the opening has been closed off too
much
5) Nozzles is worn or fouled
1) One phase is missing
2) Electric motor failure
3) Fuel does not reach the pump
4) No fuel in the tank
5) The gate on the intake pipe is closed
6) Nozzles is plugged
7) Motor (three-phase) rotates in the wrong
direction
8) Bottom valve leaking or is plugged
9) Pump failure
10) Solenoid valve failure
11) Voltage too low
1) Diameter of the pipes is too small
2) Air infiltration into the pipes
3) Gas trap filter fouled
4) Distance between the tank and burner
is too great or there are many accidental
leaks (bends, elbows, narrowing, etc.)
5) Hoses have deteriorated
1) Thermostats (boiler or environment) or
pressure switches are open
2) Photoresistance circuit
3) No power supply because the general
circuit breaker is open or the maximum
reading meter circuit breaker has tripped
or power line blackout
4) The thermostat line has not been
prepared according to the diagram or one
of the thermostats is still open
5) Internal failure
< 42 >
REMEDY
1) Clean or replace
2) Check all smoke outlets in the boiler
and flue
3) Replace the unit
4) Clean
1) Check the entire circuit
2) Replace
3) Connect and lock in place
4) Replace
5) Reset them at the proper distance
6) Clean or, if necessary, replace
1) Recalibrate
2) Eliminate the water from the tank with
the aid of a suitable pump (never use
the burner pump for this purpose)
3) Reduce the combustion air flow
4) Correct the position of the combustion
head air regulation device
5) Replace or clean
1) Check the power supply line
2) Repair or replace
3) Check the intake piping
4) Fill the tank
5) Open the gate
6) Remove and clean it thoroughly
7) Invert one of the phases in the power
supply switch
8) Remove and clean it
9) Replace
10) Check and if necessary replace
11) Contact the company providing
electrical power
1) Replace following the instructions
2) Check and vent any air
3) Remove and wash out
4) Review the entire intake pipe route,
reducing the distance
5) Replace
1) Raise the set point or wait until they
close as the temperature or pressure
drops
2) Replace
3) Turn on the circuit breaker or wait until
power returns
4) Check connections and thermostats
5) Replace