3.2 Assigning the AS−Interface addresses
Please note
Addressing valve terminal type CPV..−GE−ASI−8E6A−Z is
only permitted with addressers as per specification 2.1.
Other addressers do not permit clear access to the
slaves and in some cases overwrite the ID1 codes.
Recommendation: Use the Festo addresser type ASI−PRG−
ADR with adapter cable type KASI−ADR.
Factory setting:
The addressing device scans the existing slaves in the
AS−Interface network.
Assign the desired addresses to the two slaves one
S
after the other.
Operation with AS−Interface masters < Spec. 2.1
Operation with AS−Interface masters < Spec. 2.1 is possible
but both slaves must be programmed as A slave.
Recommendation: For operation with AS−Interface masters
< Spec. 2.1 use valve terminal type CPV..−GE−ASI−8E8A−Z
instead of CPV..−GE−ASI−8E6A−Z.
18
Slave 1: address #1, A slave
Slave 2: address #1, B slave
Festo CPV..−GE−ASI−8E6A−Z 0802a English