Festo CPV-GE-ASI-8E6A-Z Serie Manual De Instrucciones página 22

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
3.5 Connecting the AS−interface bus and the load voltage
Please note
The sensor power supply for the inputs is provided via
the AS−Interface bus.
The power supply for the valves (outputs) is provided
by the additional supply: The valves must be supplied
separately with 24 V via the load voltage connection.
The AS−Interface has an integrated watchdog function
which resets the outputs if there is a bus communica
tion failure.
Warning
Use power supplies which guarantee reliable electrical
isolation of the operating voltage as per IEC/DIN EN
60204−1. Consider also the general requirements for
PELV circuits in accordance with IEC/DIN EN 60204−1.
By the use of PELV circuits, protection against electric
shock (protection against direct and indirect contact) is
guaranteed in accordance with IEC/EN 60204−1 (Electri
cal equipment for machines, General requirements).
22
Festo CPV..−GE−ASI−8E6A−Z 0802a English

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cpv ge-asi-8e6a-z m8 serie

Tabla de contenido