Installation/Deinstallation
4.1
Steps for mounting the extension modules
The MSI 400 system is only suitable for mounting
in the switch cabinet with a minimum protection
class of IP 54.
WARNING
In an MSI 400 system, the MSI 4xx base module is on the far
left, immediately followed by both optional gateways on the
right. Then followed by the extension modules.
Make sure appropriate ESD protective measures are maintained
when mounting. Otherwise, the internal safety bus may be
damaged.
The connection between the modules is done via the integrated
connector in the housing.
Please note, when replacing a module, the MSI 400 modules
are pushed apart approx. 10 mm before the corresponding
module can be removed from the standard rail.
Take the appropriate measures to prevent foreign objects from
obstructing the connector openings.
Mount acc. to EN 50274.
The modules are contained in a 22.5 mm wide installation
housing for 35 mm standard rails in accordance with EN 60715.
Mounting the module
4.1.1
Pull the latching foot outwards with a screwdriver.
Hook the module onto the standard rail.
Important! Make sure the shield spring is seated correctly. The
module's shield springs must be securely attached to the
standard rail and have a good electrical contact.
Swivel the module onto the standard rail.
Slide the latching foot against the standard rail with a
screwdriver until the latching foot snaps into place with an
audible CLICK.
Leuze electronic GmbH + Co. KG
info@leuze.de
•
www.leuze.com
Make sure that the module is firmly mounted onto the standard
rail. Try to remove the module from the standard rail with a little
pressure. If the module remains firmly connected to the rail with
this test, the mounting is correct.
If multiple modules are mounted:
Slide the individual modules together in the direction of the
arrow until the lateral connector between the modules audibly
snaps into place.
Install an end terminal on the leftmost module and the
rightmost module.
After mounting
4.1.2
After mounting the modules, the following steps are required:
Electrically connect the modules.
Configure the modules.
Check installation before initial commissioning.
4.2
Steps for removing the extension modules
Disconnect the MSI 400 system from the power supply.
Remove the plug-in block terminals with the wiring and the end
terminals.
Slide the modules apart separately in the direction of the arrow
until the lateral connector is disconnected.