Fault code
Fault
A06
No flame after the ignition phase
F15 - A07
High fume temperature
Overtemperature protection
A08
intervention
Exchanger protection interven-
A09
tion
Overtemperature protection
F09
intervention
F10
Flow sensor fault
F11
Return sensor fault
Gas valve connection
A11
F12
DHW sensor fault
F13
Fume probe fault
Fume extraction duct safety
A14
device intervention
F34
Supply voltage under 180V
F35
Wrong supply frequency
A23-A24-A26-F20
Pressure sensor fault
F21-F40-F47-F51
F37
Incorrect system water pressure
F39
External probe fault
F19
Card parameter fault
340
BlueHelix HiTech RRT H
Possible cause
Ionization electrode fault
Flame unstable
air/fume ducts obstructed
Trap blocked
Wrong calibration
Insufficient gas supply pressure
The fume probe detects an
excessive temperature
Sensor not correctly positioned
on flow pipe or damaged
No water circulation in the system Check the circulating pump
Air in the system
No water circulation in the system Check the circulating pump and heating system
Poor circulation and anomalous
flow probe temperature increase
blocked exchanger
Flow sensor damaged
No water circulation in the system Check the circulating pump and heating system
Air in the system
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Damaged electrical connection
between the control unit and gas
valve
Sensor damaged
Wiring shorted
Wiring disconnected
Probe damaged
Wiring shorted
Wiring disconnected
Fault A07 generated 3 times in
the last 24 hours
Electric mains trouble
Electric mains trouble
Wrongly configured parameter
System pressure problems
(transducer)
b06 set to 3
Pressure too low
Water pressure switch damaged
or disconnected
Probe damaged or wiring shorted Check the wiring or replace the sensor
Probe disconnected after activa-
ting the sliding temperature
Wrong card parameter setting
cod. 3541V480 - Rev. 00 - 04/2021
Cure
Check the position of the ionization electrode, free
it from any encrustations and do the Calibration
procedure [AUTO SETUP]. Replace the electrode
if necessary.
Check the burner
Remove the obstruction from the flue, fume extrac-
tion ducts, air inlet and terminals
Check the trap and clean it if necessary
Do the Calibration procedure [AUTO SETUP].
Check the gas supply pressure
Check the exchanger
Check the flue gas probe
Check the flue material parameter
Check the correct positioning and operation of the
heating sensor and replace it if necessary
Vent the system
Vent the system
check the exchanger and system
Check correct positioning and operation of the flow
sensor and replace it if necessary
Vent the system
Check the wiring or replace the sensor
Check the wiring or replace the sensor
check the wiring, or replace the valve
Check the wiring or replace the sensor
Check the wiring or replace the fume probe
See fault A07
Check the electrical system
Check the electrical system
Check if the parameter b04 is correctly configured
System pressure value outside set limits (transdu-
cer)
Fill the system
Check the water pressure switch
Reconnect the external probe or disable the sliding
temperature
Check and if necessary modify parameter b15 to 3