Feed And Load Wiring Overview; Temporary Lighting - Lutron LCP128 Serie Guia De Instalacion

Paneles de atenuación e interruptores
Ocultar thumbs Ver también para LCP128 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 21
Wiring
(continued)

Feed and Load Wiring Overview

Feed Wiring (Mains Voltage Wiring)
• Preferred feed wiring entry for panels with main lugs/isolation switch is from the bottom left of the panel.
• Preferred feed wiring entry for feed-through panels is from the top or bottom left of the panel, wired directly to
module terminal blocks.
• Run wiring so that line (mains) voltage wiring will be at least 6 ft. (1.83 m) from sound or electronic equipment and
its wiring.
• Refer to Feed Wiring pages for more information.
Load Circuit Wiring
• Connect load wiring to the appropriate terminal block set for each module.
• For 230 V
and 240 V
DL and L.
• The Dimmed Hot/Live (DH/DL) terminal block is grouped with a numbered Hot/Live (H/L) (H1, H2, etc./L1, L2,
etc.). The number represents both the module and circuit breaker number.
• Output terminal blocks accept one #14-#10 AWG (2.5-4.0 mm
panel.
• Refer to Load Wiring pages for more information.
Caution! Common neutrals are not
permitted. Run separate neutrals for each
load circuit.

Temporary Lighting

You do not need to install a temporary distribution
panel. Connect load wires into the appropriate
terminal blocks. Each input breaker can supply
power to a load while the bypass jumper protects
the module from load faults.
Caution! Verify that the panel is fed from
the correct voltage. A feed miswire or loss
of a feed neutral can cause over-voltage
damage to the equipment. Do NOT
remove bypass jumpers at this point--they
protect the modules from load faults.
10
Installation Guide for Dimming and Switching Panels
panels, "Hot" is referred to as "Live". Therefore, terminals will be labeled
2
) wires. Preferred entry is from the top left of the
Caution! Panels require entry of wires as
specified. Improper entry will block
serviceable parts and impede air flow
through the panel.
Input circuit breaker
Bypass jumper protects the
module from load faults.
R

Publicidad

Tabla de contenido
loading

Tabla de contenido