Grafik Systems (Lp) Panels; Grafik Systems (Ccp) Panels - Lutron LCP128 Serie Guia De Instalacion

Paneles de atenuación e interruptores
Ocultar thumbs Ver también para LCP128 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 21
Panel Model Number Guide
GRAFIK Systems
Example
C C P - 2 X 2 L 1 A 4 T- 1 2 0 4 M L - 2 0 - C G P _ _ _
Prefix
Modules:
Quantity and Type
Prefix
CCP = Custom combination panel
Module Types
_X _L _A _M _F _T
List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.
X = Four-Circuit Switching (Relay) (XP)
L = Four-Circuit Dimming (4U)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
F = Four-Circuit Quiet Fan Speed (4FSQ)
T = 0-10 V, DALI (broadcast), DSI, and PWM
Ballast Control (TVM)
Feed Voltage
120 for 120 V
Module Quantity Limits
Panel Size
Feed type
Mini
Feed-through
Mini
Feed-through
Mini
Breakers
Mini
Breakers
Standard
Feed-through
Standard
Feed-through
Standard
Breakers (main lugs)
Standard
Breakers (main lugs)
Standard
Breakers (main lugs)
Standard
Breakers (main lugs)
Notes
• Consult Lutron for panels with custom breaker needs.
• TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
• TVM = NA is not TVM-ready
4
Installation Guide for Dimming and Switching Panels
(CCP) (120 V
TM
Feed
Branch
Voltage
Circuit
Feed
Breaker
Type
Rating
TVM
4A
NA
Any combination up to 3 modules
0-4
Any combination up to 2 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
NA
Any combination up to 3 modules
0-4
Any combination up to 2 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
NA
Any combination up to 9 modules
0-12
Any combination up to 8 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
NA
Any combination up to 9 modules
NA
Any combination up to 7 modules
0-12
Any combination up to 8 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
0-12
Any combination up to 5 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
(continued)
only)
Custom
Panel Suffix
(contact Lutron for custom options)
Feed Type / Input Ratings
FT = feed-through panel (circuit breakers not included) /
120 V
3M or 3ML = 1 phase 3 wire feed (split phase) / 120/240 V
4M or 4ML = 3 phase 4 wire feed / 120/208 V
2 = 1 phase 2 wire input breakers (mini only)
3 = 1 phase 3 wire input breakers (mini only)
4 = 3 phase 4 wire input breakers (mini only)
Branch Circuit Breaker Rating
20 = 20 A branch circuit breakers
15 = 15 A branch circuit breakers
Custom Panel Suffix (optional)
Indicates panel with special options
Frequency
(All Model Numbers and Voltages): 50/60 Hz
Output (Load) Ratings
Module Type Rating
XP, 4U
16 A per circuit
4A
16 A per module, 10 A per output
4M
16 A per module, 5 A per output
(1/4 HP motor)
4FSQ
2 A per output (single ceiling fan)
TVM
50 mA per channel, 750 mA per system
4U
4M
XP
0
0
0
0
R

Publicidad

Tabla de contenido
loading

Tabla de contenido