Technical Data - Bosch FLM-320-EOL4W-S Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 11
10
en
Notes
-
-
-
-
Functions
The FLM-320-EOL4W-S is used to terminate conventional stubs. It can detect faults on the
conventional line and auxiliary voltage in accordance with EN 54-13, and uses the line to
report an error on the fire panel's operating panel.
Connection
Description
Function
CONV b+
Conventional line, incoming
CONV a-
POWER +U
Power supply
POWER 0V
Shield
Cable shielding
Connect the EOL module as the last element in a conventional line. Set the resistance (R), the
voltage (V), and the power (P) for the line via the DIP switches, using the FSP-5000-RPS
programming software to calculate the values and the associated DIP settings.

Technical data

AUX input voltage
Conventional input voltage
AUX current consumption
Conventional current consumption
Housing material
Housing color
Dimensions (H x W x D)
Weight
Permitted operating temperature
Permitted storage temperature
Permitted relative humidity
Protection class compliant with IEC 60529
F.01U.121.918 | 5.0 | 2011.05
Installation must only be performed by authorized and specialized personnel!
An EOL module must be connected at the end of every conventional line.
Country-specific standards and guidelines must be observed during installation.
You are required to use the FSP-5000-RPS programming software for the FPA-5000 fire
panel to calculate which programming is required via the DIP switches.
8 VDC to 30 VDC
9 VDC to 30 VDC
< 5.5 mA
< 2.0 mA
ABS + PC blend
Signal white, RAL 9003
Approx. 126 x 126 x 71 mm
342 g
-20 °C to 55 °C
-25 °C to 85 °C
<96%, non-condensing
IP 54
FLM-320-EOL4W-S
R
V
P
POWER
CONV
Shield
+U 0V
b+