Dust-Explosion Protection Zone 20; Dust-Explosion Protection Zone 0/20 - ABB TTF300 Instrucciones Para La Puesta En Funcionamiento

Transmisor de temperatura para montaje en campo
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 105
Electrical connections
4.5.6

Dust-explosion protection Zone 20

Transmitter design: ATEX II 1D IP 65 T135 °C
Fig. 15
A Sensor
B Transmitter TTF300
C Power supply
The electric circuit of the transmitter must be limited by an upstream fuse per IEC 127 with a
fuse current rating of 32 mA. This is not required if the power supply is in intrinsically safe "ia"
design.
26 - EN
Explosion-protection zone 20
J
A
E
B
D Fuse, 32 mA
E Interface for LC display
TTF300
Safety area
D
C
A00130
CI/TTF300-X1