Safety instructions

Safety instructions for the installation according to UL or UR

2.4
Safety instructions for the installation according to U
Warnings!
ƒ
ƒ
ƒ
ƒ
Type
E94APNE1004
E94APNE2454
38
Maximum surrounding air temperature: 55 °C.
Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than 18000 rms
symetrical amperes, 500 V max., when protected by H or K5 fuses.
Voltage of the fuses must at least be suitable with the input voltage of the
drive.
Use 60/75 °C copper wire only, except for control circuits.
Branch circuit protection
Fuse [A]
100
250
or U
L
R
EDK94PNE245 DE/EN/FR/ES/IT 1.0