Setting Procedure - Tripp-Lite APS PowerVerter Manual De Operación

Ocultar thumbs Ver también para APS PowerVerter:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

200106010 230V APS Owners Manual.qxd
Configuration
• Equalize Battery Charge
This DIP Switch is momentarily engaged to begin the process of equalizing the internal resistance
of your battery's cells. This can extend the useful life of certain types of batteries; consult with
your battery's manufacturer to determine if your batteries could benefit from this process. The
charge equalization process is automatic and once started can only be stopped by removing the
input power.

Setting Procedure

• Move to "Equalize" (DOWN) position for three seconds.
• Move to "Reset" (UP) position and leave it there.
CAUTION: Battery charge equalization should only be performed in
strict accordance with the battery manufacturer's instructions and
specifications.
CAUTION: Do not leave DIP switch #3 in the down position after
beginning process.
Battery Charge
Reset
Equalize
* Factory default setting.
• Limit Battery Charger
To prevent overheating smaller batteries, the charger on this UPS system is initially set to deliver only
a fraction of its maximum power rating to connected batteries. If you are using this system with a
larger (over 100 amp-hours) battery or battery system, you may switch your battery charger to full
power without overheating your batteries.
Battery Charger
Partial (1/3) Charging Power
Full Charging Power
* Factory default setting.
1/3/02
5:18 PM
continued
(DIP Switch #3, Group B)
Switch Position
Up*
Down
(DIP Switch #4, Group B) (APSINT1524 only)
Switch Position
Up*
Down
7
Page 7
4 3 2 1
Reset*
Equalize
4 3 2 1
Partial*
Full

Publicidad

Capítulos

Tabla de contenido
loading