Connecting the control unit with 230V single-phase power supply
Connecting the control unit with 230V three-phase power supply
Connecting the control unit with 400V three-phase power supply
2.3) Descriptions of connections:
All the connections are made by means of special terminals located
on the lower side of the electronic card. Only the power input line
should enter the upper part, directly connected to the overload cut-
out terminals.
To connect the earth circuit to the control unit and motor, use
terminals 6-7 wherever possible.
A brief description of the possible connections of the control unit outputs follows.
1-2
:
Flashing light
3-4-5
:
Motor
6-7
:
Earth
8-9
:
Phototest
10
:
Open limit switch
11
:
Common
12
:
Close limit switch
13-14
:
24 Vac
15
:
Common
16
:
Gate open indicator
17
:
Stop
18
:
Photocell
19
:
Step-by-step
20
:
Open
21
:
Close
41-42
:
2° Radio Ch
43-44
:
Aerial
There are two additional slots on the unit card for optional cards:
RADIO
PIU
We recommend waiting until installation is complete before plugging in the optional RADIO or PIU cards.
The optional cards are not essential for system operation and, if used, they make troubleshooting more complicated.
230 V Single-phase
L
N
230 V Three-phase
R
S
T
400 V Three-phase
R
S
T
= Connection to 220 Vac max. 40W flashing light
= Line to motor 230Vac / 400Vac
= Control unit and motor earth connection
= 24 Vac output to power photoelectric cell transmitters (Max. 200mA)
= OPEN limit switch input
= Common for limit switch inputs
= CLOSE limit switch input
= 24 Vac output to accessories Max. 200mA (400mA if phototest is not used)
= Common for all inputs
= Max. 24 Vac output for gate open indicator 2W
= Input with STOP function (Emergency, shutdown or extreme safety)
= Input for safety devices (photoelectric cells, pneumatic edges)
= Input for cyclic functioning (OPEN STOP CLOSE STOP)
= Input for opening
= Input for closing
= Output for the second radio receiver channel, if any
= Input for the radio receiver aerial
=Slot for NICE radio receivers
=Slot for "PIU" expansion card with extra functions
F2= 0.5 A
M
230 V
F2= 0.5 A
M
230 V
F2= 0.5 A
M
400 V
If the control unit is powered by a single-phase system just two wires
must be connected to the first two terminals to the left of the overload
cut-out (the third terminal being unused). Connect the single-phase
motor and relative condenser as shown in figure 3a.
Take care when selecting 400V or 230V input voltage.