6
Electrical installation
Connection data
{
Danger!
Hazardous electrical voltage
The leakage current of the connected controllers to PE can amount to
> 3.5 mA AC or > 10 mA DC.
Possible consequences:
Death or severe personal injury if the device is touched in the event of an
ƒ
error.
Protective measures:
Implement the measures required in the EN 61800−5−1, particularly
ƒ
– Fixed installation
– Provide a standard PE connection (PE conductor diameter ³ 10 mm
connect PE conductor twice)
Connection data
Sinusoidal filter
EZS3−004A200
EZS3−010A200
EZS3−017A200
EZS3−024A200
EZS3−032A200
EZS3−037A200
EZS3−048A200
EZS3−061A200
EZS3−072A200
EZS3−090A200
44
Terminal
Connection
cross−sections
2
[mm
]
[AWG]
0.2 ... 6
24 ... 10
0.5 ... 16
20 ... 6
2.5 ... 25
10 ... 6
2.5 ... 35
12 ... 2
16 ... 50
1/0 ... 6
l
Tightening torque
[Nm]
[lb−in]
0.6
5.3
1.5
13.3
2
17.7
3
26.5
EDKZS3X200 DE/EN/FR/ES/IT 4.0
2
or
PE screw
Æ
Tightening torque
[Nm]
[lb−in]
M4
2
17.7
M5
3
26.5