REV.0-05/04
Check daily
NOTE
!
Do not alter the primary conditions of regulation
and do not touch the sealed parts.
RECOIL START
1. make sure the load plugs are disconnected
or the G.F.I. switch (D) is not inserted
(intervention/insertion lever facing down),
so as to ensure the motor's start-up wi-
thout any loads inserted;
2. Accelerator at 50% speed
3. Hold the starting handle firmly.
4. Pull the rope hard and fast. Pull
it all the way out. Use two hands if
necessary.
5.Then return it slowly.
6. After starting bring at idle speed
for a few minutes according to table.
Temperature
≤ - 20° C
- 20° C / - 10° C
- 10° C / - 5° C
≥ - 5° C
STARTING - STOPPING
Time
5'
2'
1'
20"
STOPPING
To stop the engine in normal conditions attend the
following process:
- interrupt the power source, switching off all tools
connected. If a tool does not feature a po-
wer switch, lower the G.F.I. switch lever (D);
- let the engine idle for a few minutes,
-Pull the stop lever (28) until the engine
stops
To shut down the motor in an emergency situation
act immediately on the stop lever (28).
CAUTION
!
RUNNING-IN
During the first 50 hours of operation, do not use more
than 60% of the maximum output power of the unit and
check the oil level frequently, in any case please stick to
the rules given in the engine use manual.
GE 4000 LDS/GS
M
26