Assembly and maintenance instructions
Diaphragm Safety Valve
1
General Notes of Safety
• Only use the valve:
- for the intended purpose
- in satisfactory condition
- with respect for safety and potential hazards.
• Always observe the installation instructions.
• Faults that may impair safety must be addressed immediately.
• The safety valve is exclusively designed for the range of application descri-
bed in these installation instructions. Any other use, or a use exceeding the
range of application shall be considered as improper use.
• The manufacturer's warranty for the setting of the valve shall be null and void
if the sealed cover is removed.
• All assembly work is to be carried out by authorized specialist staff.
2
Range of Application
Series 651 mHNK/ mHIK/ HNs:
Solely for the protection of closed, thermostat protected heating systems with
supply temperatures of up to 120 °C. Upon failure of the temperature regulation and
limitation device the safety valves blow off the entire heating capacity of the heat
generator in the form of hot water and steam.
Series 651 mSK:
Solely for the protection of closed, intrinsically safe solar heating systems with
water or water mixtures serving as heat transfer medium with permissible supply
temperatures of up to 120 °C.The valve is able to discharge the entire heating capa-
city of the solar heating system in the form of hot water and steam.
3
General Notes
Safety valves are high-quality fittings which require a particularly careful handling.
The sealing surfaces are precision-machined at the seat and cone to attain the
required tightness. Always avoid the penetration of foreign particles into the valve
during assembly and during the operation. Rough handling of the finished valve
during storage, transportation and assembly can also result in a safety valve leaking.
If the safety valves are painted always ensure that the sliding parts do not come into
contact with the paint.
8
www.goetze-armaturen.de
en